8 Operation
40 of 68
KSB Delta Solo / KSB Delta Eco
8.1.3.1 Menu: Operation
The Operation section contains all information required for operating the machine
and the process. This includes:
▪
Login to device with password
▪
Operating and measured values for motor, frequency inverter, pump and system
▪
Setpoints and control values
▪
Energy meter and operating hours
8.1.3.1.1 Access levels
Three access levels have been defined to prevent unintentional or unauthorised
access to frequency inverter parameters:
Table 13:
Access levels
Access level
Description
Standard (No Login)
Access without password entry.
Customer
Access level for the expert user with access to all parameters required for
commissioning
Customer service
Access level for service personnel.
If a parameter's access level is not explicitly specified, the parameter is always
assigned the
Customer
access level.
Table 14:
Access level parameters
Parameter Description
Possible settings
Factory setting
1-1-1
Customer Login
Log in as customer
0000...9999
0000
Customer service parameters can only be accessed using the KSB ServiceTool and the
appropriate dongle.
NOTE
If no keys are pressed for five minutes, the system will automatically return to the
Standard
access level..
The password can be changed after entering the factory default password.
Table 15:
Parameter for changing the password (requires use of the KSB ServiceTool)
Parameter Description
Possible settings
Factory setting
1-1-5
Customer Access ID
Changing the customer access ID
0000...9999
-
8.1.3.2 Menu: Diagnosis
In the Diagnosis section, the user is provided with information about faults and
warning messages that pertain to the pump set or process. The frequency inverter
can be in fault (standstill) or warning (operational) status. The user can also find
previous messages in the history.
Messages
All monitoring and protective functions trigger warnings or alerts. These are
signalled via the amber or red LED of the LED traffic light function.
A corresponding message is output on the control panel display. If more than one
message is output, the last one is displayed. Alerts have priority over warnings.
Pending messages
If a message has occurred and been acknowledged but has not gone, this message
will be listed in the Pending Messages menu. All current messages can be displayed in
the Diagnosis menu under Pending Messages (
2-1
). Active warnings and alerts can
also be connected to the relay outputs.