7.2.4 Open-loop control
Function
In Open-loop Control operating mode the pump set runs at a set speed. The speed
can be set to one of three speed levels.
Setting
Table 16:
Selecting Open-loop Control and the setpoint
Step 1: Activating the setting mode
▪
Press and hold the control button (
●
) for 3 seconds
– This will activate the display backlighting.
– The flashing symbol indicates the active operating mode.
Step 2: Selecting the Open-loop Control operating mode
▪
Press the control button (
●
) for a minimum of 0.5 seconds until
the symbol for Open-loop Control flashes.
Step 3: Changing the setpoint
▪
Increase or decrease the setpoint by pressing the control
buttons (+) or (-) respectively.
– The bar diagram shows the active speed level.
Setpoint 1 = 1 bar flashes
Setpoint 2 = 2 bars flash
Setpoint 3 = 3 bars flash
-
Step 4: Confirming the current setpoint
▪
Press and hold the control button (
●
) for a minimum of 3
seconds.
– The set setpoint flashes and is saved.
H
Q
1
1
2
3
Fig. 13:
Open-loop Control settings
Table 17:
Speeds depending on the speed level
Size
Speed
Speed level 1
Speed level 2
Speed level 3
[rpm]
[rpm]
[rpm]
15-40-130
1400
2150
2750
15-60-130
2150
3000
3400
25-40-130
1400
2150
2750
25-60-130
2150
3000
3400
25-40
1400
2150
2750
25-60
2150
3000
3400
25-80
2000
3000
3950
30-40
1400
2150
2750
30-60
2150
3000
3400
30-80
2000
3000
3950