5 Installation at Site
20 of 52
Calio S
1157.8117/01-EN
Permissible installation positions
Fig. 3:
Permissible installation positions
Screw-ended pump
1. Position the pump set as indicated in an easily accessible place.
ð
An arrow on the pump casing and thermal insulation shell indicates the
direction of flow.
2. Accurately insert the sealing element.
3. Connect the pump and piping with a pipe union.
4. Tighten the pipe union hand-tight with a suitable tool.
5. Accurately insert the sealing element in the opposite pipe union.
6. Tighten the pipe union hand-tight with a suitable tool.
5.4 Connecting the piping
WARNING
Hot surface
Risk of burns
▷
Never touch a pump set when it is in operation.
WARNING
Impermissible loads acting on the pump nozzles
Risk of burns by hot fluids escaping!
▷
Do not use the pump as an anchorage point for the piping.
▷
Anchor the pipes in close proximity to the pump and connect them without
transmitting any stresses or strains.
▷
Take appropriate measures to compensate for thermal expansion of the piping.
CAUTION
Contamination/dirt in the piping
Damage to the pump!
▷
Flush the piping prior to commissioning or replacing the pump. Remove any
foreign matter.