5 Installation at Site
24 of 84
Amarex N
2563.84/08-EN
Table 9:
Chemical anchor dimensions
Size
(d
1
× l
1
)
d
2
t
1
t
2
SW
1
5)
SW
2
5)
M
d1
[mm] [mm] [mm] [mm] [mm]
[Nm]
M10 × 130
12
20
90
17
7
20
M16 × 190
18
35
125
24
12
60
Table 10:
Curing times of mortar cartridge
Floor temperature
Curing time
[°C]
[min]
-5 to 0
240
0 to +10
45
+10 to +20
20
> +20
10
5.3.1.2 Connecting the piping
DANGER
Impermissible loads acting on the flange of the duckfoot bend
Danger to life from escaping hot, toxic, corrosive or flammable fluids!
▷
Do not use the pump as an anchorage point for the piping.
▷
Anchor the pipes in close proximity to the pump and connect them without
transmitting any stresses or strains.
▷
Observe the permissible flange loads.
▷
Take appropriate measures to compensate for thermal expansion of the piping.
NOTE
When the pump set is used for draining low-level building areas, install a swing
check valve in the discharge line to avoid backflow from the sewer system.
CAUTION
Critical speed
Increased vibrations!
Damage to mechanical seals and bearings!
▷
Install a swing check valve in longer riser pipes to prevent the pump from
excessive running in reverse.
When fitting a swing check valve, make sure that the unit can still be vented
properly.
5)
SW = Width across flats