9
Use
Body Showers with pull rod
Pull the lever handle all the way down to the valve lever limit stop.
After the shower has started:
Remove all contaminated clothing which is not stuck to your skin, and rinse all affected areas with
cool, clean water. EN and ANSI standards recommend flushing for 15 minutes continuously, seek
your local safety regulations for further advice and recommendations.
In order to stop the shower, push the pull rod lever up, until the valve is closed.
Seek medical attention!
Models with Optional Eye Shower
Rotate/push the actuating lever a quarter turn in order to start the eye/face wash shower. After
doing so, the dust cover move from the eye/face shower as a result of the first surge of water starts.
The eye shower should not make direct contact with the contaminated eye or any surrounding areas.
Ideal rinsing is assured at a distance of approximately 15 cm (seek your local safety regulations for
further advice and recommendations).
In order to stop the shower, pull the lever up until the valve is closed.
Seek medical attention!
Models with Optional Heater
If an electrical heating is installed, it has been connected by a licensed electrician and is functioning
correctly when the unit has left our warehouse. In this connection the safety instructions have been
followed. A maximum water temperature of approximately +25° C is preset at the factory. The
temperature can be conveniently checked with the thermometer (optional).
This temperature may be fallen short of, depending upon local conditions at the installation site
(wind-chill factor etc.). The heaters are equipped with a regulator, by means of which the
temperature can be adjusted if required (see details in separately enclosed instructions for use). The
operation manual from the supplier is included when the item is shipped to the purchaser. The
submersible heating element is designed to work when the trailer is connected to its power source
and the water temperature has been detected that it is below approximately 15°C. It will then
operate until the water contained in the tank will reach approximately 25°C and then switch off
again.
Red light as seen below means the heating element is working. Please be aware that there is a
automatic cut off switch installed for the heating element. This prevents the heating element
working when there is an insufficent amount of water contained in the tank, thus avioding the heater
to over heat.
Summary of Contents for 7023