7.3.11 Overheating Programme - Anti-legionella
Programme heats water to 65
°C, to remove potential legionella bacteria.
Activation can be automatic or manual.
NOTE
The device overheats water and destroys the Legionella bacteria in
the water tank. For complete disinfection a hot water flow through
all pipes of the water installation must be ensured.
NOTE
Factory preset overheating is automatic every 14 days. We advise
against overheating too often, as energy consumption during
overheating is 1/3 higher than during normal operation.
7.3.12 Automatic Quick Water Heating
Programme "Quick water heating"
(chapter 8.3.2
) can be triggered automatically
when water temperature falls below the set value.
Move between setup windows with the key
.
Enter setting with the
key
.
Turn
programme »
ON
«
or »
OFF
«...
Set temperature at which
the "Quick Water
Heating" programme
activates.
7.3.13 Screen Brightness
Screen brightness settings.
Parameters from lowest to full brightness:
7.3.14 System Information
In the System information menu data on software and hardware of the
controller, display and Optitronic Web module (optionally) are given.