BIC · Edition 09.22
EN-4
➔
Insulate the ceramic tube at least as far as the
burner head, to a maximum of 20 mm (0.8 inches)
behind the burner head.
➔
Burners without extension:
A/B
> 10 mm > 0,394
"
≤ 15 mm
≤ 0,591"
➔
Burners with extension:
A/B
> 10 mm
> 0,394
"
≤ 15 mm
≤ 0,591"
3.3 Installation on the furnace
➔
When installing, always ensure that when the burner
is mounted, it is sealed tightly on the furnace wall.
1
2
3
TSC 65AO48
-300/35-S
i1500
Si-1500
➔
Attach the ceramic tube type label.
4
5
3.4 Air connection, gas connection
BIC
GA
LA
BICW
GA
LA
(14,16,17)
type
Gas connec-
tion GA
Air connec-
tion LA*
BIC 50
Rp 1/2
Rp 1/2
BICA 65
Rp 1/2
Ø 48 mm
BIC 65
Rp 3/4
Rp 1 1/2
BIC 80
Rp 3/4
Rp 2
BIC 100
Rp 1
Rp 2
BIC 125
Rp 1 1/2
DN 65
BIC 140
Rp 1 1/2
DN 80
BICW 65
Rp 3/4
DN 65
BICW 80
Rp 3/4
DN 80
BICW 100
Rp 1
DN 80
BICW 125
Rp 1 1/2
DN 100
BICW 140
Rp 1 1/2
DN 125
* Up to burner size 100, threaded connection;
as from burner size 125, flanged connection,
BICA 65: tube connection.
➔
Threaded connection to DIN 2999, flange dimen-
sions to DIN 2633, PN 16.
➔
Install flexible tubes or bellows units to prevent
mechanical stress or transmission of vibration.
➔
Ensure that the gaskets are undamaged.
DAnGeR
Risk of explosion!
– Ensure the connection is air-tight.
➔
On delivery, the threaded gas connection is situated
opposite the air connection; it can be rotated in
increments of 90°.
3.5 Connection to AnsI/nPt
➔
An adapter set is required for connection to ANSI/