Valve housing: aluminium,
valve seal: NBR.
Connection flanges:
VAS/VCS 1 – 3 with internal thread:

Rp pursuant to ISO 7-1, NPT pursuant to ANSI/

ASME;
VAS/VCS of size 2 and higher: with PN 16 ISO 
flange (pursuant to ISO 7005), with ANSI flange 

pursuant to ANSI 150.

Electrical data

Cable gland: M20 x 1.5.
Electrical connection: cable with max. 2.5 mm

2

 

(AWG 12) or plug with socket to EN 175301-803.
Duty cycle: 100%.
Power factor of the solenoid coil: cos φ = 0.9.
Mains voltage:
230 V AC, +10/-15%, 50/60 Hz;
200 V AC, +10/-15%, 50/60 Hz;

120 V AC, +10/-15%, 50/60 Hz;
100 V AC, +10/-15%, 50/60 Hz;

24 V DC, ±20%.
Power consumption:

Type

Voltage

Power

VAS 1

24 V DC

25 W

100 V AC

25 W (26 VA)

120 V AC

25 W (26 VA)

200 V AC

25 W (26 VA)

230 V AC

25 W (26 VA)

VAS 2, VAS 3

24 V DC

36 W

100 V AC

36 W (40 VA)

120 V AC

40 W (44 VA)

200 V AC

40 W (44 VA)

230 V AC

40 W (44 VA)

VBY

24 V DC

8 W

120 V AC

8 W

230 V AC

9.5 W

Contact rating of proof of closure switch:

Type

Voltage

Min. current 

(resistive 

load)

Max. cur-

rent (resis-

tive load)

VAS..S

12 – 250 V AC, 

50/60 Hz

100 mA

3 A

VAS..G 12 – 30 V DC

2 mA

0.1 A

Switching frequency of proof of closure switch: 
max. 5 x per minute.

Switching 
current [A]

Switching cycles*

cos φ = 1

cos φ = 0.6

0.1

500,000

500,000

0.5

300,000

250,000

1

200,000

100,000

3

100,000

*  Limited to max. 200,000 cycles for heating 

systems.

Air flow rate Q

Air flow rate Q for a pressure loss of ∆p = 1 mbar 

(0.4 "WC)

∆p 1 mbar (0,4 "WC)

1 x VAS

∆p 10 mbar (4 "WC)

1 x VBY/1 x VAS 1

Type

Air flow rate

Q [m

3

/h]

Q [SCFH]

VAS 110

4.4

155.4

VAS 115

5.6

197.7

VAS 120

8.4

296.6

VAS 125

9.5

335.5

VAS 225

16.7

589.7

VAS 232

21

741.5

VAS 240

23.2

819.2

VAS 250

23.7

836.8

VAS 340

33.6

1186.4

VAS 350

36.4

1285.3

VAS 365

37.9

1338.2

Air flow rate Q for a pressure loss of ∆p = 10 mbar 
4 "WC)

∆p 1 mbar (0,4 "WC)

1 x VAS

∆p 10 mbar (4 "WC)

1 x VBY/1 x VAS 1

Type

Air flow rate

Q [m

3

/h]

Q [SCFH]

Bypass valve VBY

0.85

30.01

Pilot gas valve VBY

0.89

31.43

Type

Air flow rate

Ø [mm]

[m

3

/h]

Ø ["]

[SCFH]

Bypass valve 

VAS 1

1

0.2

0.04

7.8

2

0.5

0.08

17.7

3

0.8

0.12

28.2

4

1.5

0.16

53.1

5

2.3

0.20

81.2

6

3.1

0.24

109.5

7

3.9

0.28

137.7

8

5.1

0.31

180.1

9

6.2

0.35

218.9

10

7.2

0.39

254.2

Pilot gas valve 

VAS 1

10

8.4

0.39

296.6

Safety information in accordance 
with EN 61508-

See Technical Information VAS, VCS (D, GB, F) – 
www.docuthek.com

Summary of Contents for VAS Series

Page 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 17 The following c...

Page 2: ...ve is not damaged during installation and operation Sealing material and dirt e g thread cuttings must not be allowed to get into the valve hous ing A filter must be installed upstream of every sys te...

Page 3: ...lenoid valve VAS 1 a DN 25 differential pressure orifice with outlet opening d 30 mm 1 18 must be inserted at the outlet of the pressure regulator In the case of pressure regulator VAx 115 or VAx 120...

Page 4: ...ing Type 2 the en closure openings shall be closed with fittings rated UL Type 2 3 3R 3RX 3S 3SX 3X 4X 5 6 6P 12 12K or 13 Gas solenoid valves shall be protected by a branch circuit protective device...

Page 5: ...re is a risk of interference between valve voltage and proof of closure switch voltage To make wiring easier the connection terminal for the proof of closure switch can be removed 1 3 2 LV1 N 1 3 2 LV...

Page 6: ...if the adjusting screw is overturned Setting the start gas rate on VAS L VCS L The start gas rate can be set by turning the damping unit a maximum of 5 turns There must be a period of 20 seconds betwe...

Page 7: ...VAS 2 3 use the small seal from the actuator adapter set and only one of the large seals VAS 1 3 10 11 Slide seal under the second groove 12 Position new actuator 13 Follow the reverse procedure when...

Page 8: ...4 5 3 10 9 Maintenance CAUTION In order to ensure smooth operation check the tightness and function of the VAS Once per year twice per year in the case of biogas check for internal and external tight...

Page 9: ...ion from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Bypass pilot gas valves 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Pr...

Page 10: ...10 mm 0 39 at the outlet of the main valve if the bypass valve s outlet flange is designed as a blind flange For the pilot gas valve insert sealing plug F at the outlet of the main valve if the pilot...

Page 11: ...s piloto ppna bypass eller t ndgasven tilen pne bypass eller tenn gassventilen Otev t obto kov ventil nebo zapalovac plynov ventil Otworzy zaw r obej ciowy lub zaw r gazu zap onowego Tightness control...

Page 12: ...nnect the system from the electrical power supply Shut off the gas supply 16 5 4 3 8 7 6 9 10 13 12 11 15 14 In both connection boxes push through the knock out for the cable gland set then remove the...

Page 13: ...AMSL Ambient temperature 20 to 60 C 4 to 140 F no condensation permitted Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the servic...

Page 14: ...3 A VAS G 12 30 V DC 2 mA 0 1 A Switching frequency of proof of closure switch max 5 x per minute Switching current A Switching cycles cos 1 cos 0 6 0 1 500 000 500 000 0 5 300 000 250 000 1 200 000 1...

Page 15: ...in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby decl...

Page 16: ...earch Class 7400 and 7411 Safety overpressure slam shut valves Designed for applications pursuant to NFPA 85 and NFPA 86 ANSI CSA approved Canadian Standards Association ANSI Z21 21 and CSA 6 5 UL lis...

Reviews: