4.3 Information and functions
In general, SD 200 W/R indicators will always act at operator level.
Display value and measuring unit
•
This is the main display information of the indicator. After selecting any other information, it
will always return to this main display automatically.
Under range / Over range
•
If the current is in-between 3.5 mA and 3.75 mA the value
“
-----
“
will be displayed.
•
If the input current is in-between 3.75 mA and 4 mA the value corresponding to 4 mA will be
displayed.
•
If the input current is in-between 20 mA and 21.5 mA the value will be extrapolated while an
message is displayed
“
RANGE ERROR
”
.
•
If the input current is above 21.5 mA the value
“
9999
”
and
“
Error high
”
will be displayed.
•
If the input current is above 25 mA the value
“
9999
”
and
“
Error SC
”
(short circuit) will be
displayed.
4.4 Configuration
Configuration of the SD 200 W/R indicators is done at SETUP-level. SETUP-level is reached by
pressing the PROG/ENTER key for 7 seconds; at which time, the indication "SETUP" will be
displayed. In order to return to the operator level, PROG will have to be pressed for three
seconds. Alternatively, if no keys are pressed for 2 minutes, the unit will exit SETUP
automatically. SETUP can be reached at all times while the indicator remains fully operational.
Press the key for 7 seconds to enter the SETUP-level
Selection of function-group and function: SETUP is divided into several function-groups and
functions.
Select function-group with
Select function with
INFORMATION!
A password may be required to enter SETUP. Without this password access to SETUP is denied.