40
02/2019 - MA OPTIWAVE-M 7400 C R01 en
4
OPERATION
OPTIWAVE-M 7400 C
B
–
Test menu
Menu
No.
Function
Function description
Selection list
Marine
Default
B1 Simulation
B1.1 Set Value
B1.1.2
Level
This sets the device to a given test level
value. Make sure that menu item
min-max:
-4900.0...+5100.0 m /
1
C4.1.1 Current Out. 1 Var. is set to "Level"
before the device simulates a level value.
This procedure sends an
-192.91
+03
...+200.79
+03
in
-16076...+16732 ft
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [
^
] to confirm the
value, the display shows the question
"Start Simulation?" Push [
] or [
] to
set the display to "Yes". Push [
^
] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
procedure: Expert
B1.1.3
Distance
This sets the device to a given test
distance value. Make sure that menu
min-max:
-4900.0...+5100.0 m /
1
item C4.1.1 Current Out. 1 Var. is set to
"Distance" before the device simulates a
distance value. This procedure sends
-192.91
+03
...+200.79
+03
in
-16076...+16732 ft
an output signal that agrees with the
test reading. Output will change to the
selected value, independent of the
measurement data.
When you push [
^
] to confirm the
value, the display shows the question
"Start Simulation?" Push [
] or [
] to
set the display to "Yes". Push [
^
] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
procedure: Expert
B1.1.4
Reflection
This sets the device to a given test
reflection value. Make sure that menu
item C4.1.1 Current Out. 1 Var. is set to
"Reflection" before the device simulates a
level value. This procedure sends an
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [
^
] to confirm the value,
the display shows the question "Start
Simulation?" Push [
] or [
] to set the
display to "Yes". Push [
^
] again to start
the test. The device goes to back to
Normal mode after 1 hour.
Minimum access level to do the
procedure: Expert
min-max:
0...100%
1