4
COMMISSIONING / OPERATION
26
H250 M40 ESK4
www.krohne.com
03/2014 - 4002251801 - AD H250/M40 PROFIBUS R01 en
Diagnosis to control system in case of
•
Compatibility mode (ESK3-PA: F201hex),
•
Compatibility mode (Profile: 9740hex):
Bit
Nu
mbe
r
supported
Description
Remedy
16
yes
Error appears
-
17
yes
Error disappears
-
24
yes
Hardware failure electronics
Restart the device.
Reset the device to Factory/Default settings.
Check connection between basic module and
PROFIBUS module.
If the error occurs again: send the device back to
the manufacturer with an indication of the error.
28
yes
Memory error
Reset the device to Factory/Default settings. If the
error occurs again: send the device back to the
manufacturer with an indication of the error.
29
yes
Measurement failure
Refer to detailed diagnosis in bits 56 to 73. If no
further information is available: send the device
back to the manufacturer with an indication of the
error.
35
yes
Restart
Device is restarted because of power-up or
warmstart request. In case of unexpected restart:
send the device back to the manufacturer with an
indication of the error.
36
yes
Coldstart
Device is reset to its Factory/Default settings
because of a user request or exchange of the basic
module (serial number is changed). Recover user
specific parameter settings.
39
yes
Ident_Number violation
Ident. Number Selector was modified while cyclic
data transfer was active. To clear this message
perform one of the following actions
•
Reset Ident. Number Selector to its former
setting
•
Stop cyclic data transfer
•
Restart the device
55
yes
Extension available
Refer to detailed diagnosis in bits 56 to 73
56
1
IRAM Error
Restart the device. If the error occurs again: send
the device back to the manufacturer with an
indication of the error.
57
1
XRAM error
58
1
ROM error
59
1
SPC4 Error
60
1
ADC Error
Check environment conditions. If they are within
the specified limits: send the device back to the
manufacturer with an indication of the error.
61
1
EEPROM Error
Restart the device. If the error occurs again: send
the device back to the manufacturer with an
indication of the error.
62
1
FRAM Error
Reset the device to Factory/Default settings. If the
error occurs again: send the device back to the
manufacturer with an indication of the error.
64
1
No ADC ZeroCal
Activate linearization or carry it out again (HART
®
communication and linearization software are
required; the original calibration values must be
known), or send the device back to the
manufacturer for linearization.
65
1
No ADC FullCal