46
BM 70 M
Input the following parameters:
Tank height
6 m
Reference offset
+ 1 m
Tank bottom offset
0
The possible measuring range is:
Distance = (1 m + block distance) to 7 m.
Example 2
Reference point for level measurement
differs from the programmed tank bottom
position (in the example, 2 m below the
tank bottom).
Let the tank height be H = 6 m.
Input the following parameters:
Tank height
6 m
Tank bottom offset
+ 2 m
Reference offset
0
The possible measuring range is:
Level = 2 m to (8 m - block distance)
Example 3
Only a specific part of the level in a very
tall tank is to be measured (in the example,
levels 50m ... 60m).
Input the following parameters:
Tank height
10 m
Tank bottom offset
+ 50 m
Reference offset
0
The possible measuring range is:
Level = 50 m to (60 m - block distance).
H = 6m
BM 70 Reference point
Reference plane
for level measurement
8m
Tank bottom
TBO = 2m
Block-
distance
Level
10m
60m
tank bottom
TBO =
50m
programmed
Block
distance
BM 70 Reference point
Level
Reference plane
for level measurement
Summary of Contents for BM 70 M Series
Page 75: ...BM 70 M 75 10 Certificates and approvals 10 1 Declaration of Conformity...
Page 83: ...BM 70 M 83 Annex C Spare parts...
Page 84: ...84 BM 70 M...
Page 85: ...BM 70 M 85...
Page 102: ...16 BM 70M EEx BM 70Mi EEx 11 Approvals...
Page 103: ...BM 70M EEx BM 70Mi EEx 17...
Page 104: ...18 BM 70M EEx BM 70Mi EEx...
Page 105: ...BM 70M EEx BM 70Mi EEx 19...
Page 106: ...20 BM 70M EEx BM 70Mi EEx...
Page 107: ...BM 70M EEx BM 70Mi EEx 21...
Page 108: ...22 BM 70M EEx BM 70Mi EEx...