background image

Kramer Protocol 2000 

 

35

NOTE 5

 – For the OUTPUT byte set as 6, the VIS source is the input selected using the OUTPUT byte. Similarly, for the 

OUTPUT byte set as 7, the VIS source is the output selected using the OUTPUT byte. Note also, that on some machines the 

sync source is not software selectable, but is selected using switches, jumpers, etc!  

 

NOTE  6

  –  If  INPUT  is  set  to  127  for  these  instructions,  then,  if  the  function  is  defined  on  this  machine,  it  replies  with 

OUTPUT=1. If the function is not defined, then the machine replies with OUTPUT=0, or with an error (invalid instruction 

code).  

 

If the INPUT is set to 126 for these instructions, then, if possible, the machine will return the current setting of this function, 

even for the case that the function is not defined. For example, for a video switcher which always switches during the VIS of 

input #1, (and its VIS setting cannot be programmed otherwise), the reply to the HEX code 

0A 

FE 

80 

81 (ie. request VIS setting, with INPUT set as 126

dec

)  

would be HEX codes 

4A 

FE 

81 

81 (ie. VIS setting = 1, which is defined as VIS from input #1). 

 

NOTE 7

 – Setting OUTPUT to 0 will return the VIS source setting as defined in instruction #7. Setting to 1 will return the 

input # or output # of the sync source (for the case where the VIS source is set as 6 or as 7 in instruction #7). Setting to 2 

returns the vertical sync frequency (0 for no input sync, 50 for PAL, 60 for NTSC, 127 for error).  

 

NOTE 8

 - The reply is as in TYPE 3 above, except that here the OUTPUT is assigned with the value 0 if the setup is not 

defined / no valid input is detected; or 1 if it is defined / valid input is detected. 

 

NOTE  9

  -  An  error  code  is  returned  to  the  PC  if  an  invalid  instruction  code  was  sent  to  the  switcher,  or  if  a  parameter 

associated with the instruction is out of range (e.g. trying to save to a setup greater than the highest one, or trying to switch an 

input or output greater than the highest one defined). This code is also returned to the PC if an RS-232 instruction is sent 

while the machine is being programmed via the front panel. Reception of this code by the switcher is not valid. 

 

NOTE 10

 – This code is reserved for internal use. 

 

NOTE 11

 – For machines where the video and / or audio gain is programmable.

 

 

NOTE 12

 - Under normal conditions, the machine's present status is saved each time a change is made. The "power-down" 

save (auto-save) may be disabled using this code. Note that whenever the machine is turned on, the auto-save function is set. 

 

NOTE 13

 - This is a request to identify the switcher/s in the system. If the OUTPUT is set as 0, and the INPUT is set as 1, 2, 

5 or 7, the machine will send its name. The reply is the decimal value of the INPUT and OUTPUT. For example, for a 2216, 

the reply to the request to send the audio machine name would be (HEX codes): 

  

7D 

96 

90 

81  (i.e. 128

dec

+ 22

dec

 for 2

nd

 byte, and 128

dec

+ 16

dec

 for 3

rd

 byte). 

 

If the request for identification is sent with the INPUT set as 3 or 4, the appropriate machine will send its software version 

number. Again, the reply would be the decimal value of the INPUT and OUTPUT - the INPUT representing the number in 

front of the decimal point, and the OUTPUT representing the number after it. For example, for version 3.5, the reply to the 

request to send the version number would be (HEX codes): 

 

7D 

83 

85 

81  (i.e. 128

dec

+ 3

dec

 for 2

nd

 byte, 128

dec

+ 5

dec

 for 3

rd

 byte). 

 

If the OUTPUT is set as 1, then the ASCII coding of the lettering following the machine’ s name is sent. For example, for the 

VS-7588YC, the reply to the request to send the first suffix would be (HEX codes): 

 

7D 

D9 

C3 

81  (i.e. 128

dec

+ ASCII for “ Y” ; 128

dec

+ ASCII for “ C” ). 

 

NOTE 14

 - The number of inputs and outputs refers to the specific machine which is being addressed, not to the system. For 

example, if six 16X16 matrices are configured to make a 48X32 system (48 inputs, 32 outputs), the reply to the HEX code 

3E 

82 

81 

82 (ie. request the number of outputs)  

would be HEX codes 

7E 

82 

90 

82 

ie. 16 outputs 

 

NOTE 15

 – When the OVR bit (4

th

 byte) is set, then the “ video”  commands have universal meaning. For example, instruction 

1 (SWITCH VIDEO) will cause all units (including audio, data, etc.) to switch. Similarly, if a machine is in  “ FOLLOW”  

mode, it will perform any “ video”  instruction. 

  

NOTE 16

 - The reply to the “ REQUEST WHETHER PANEL IS LOCKED”  is as in NOTE 4 above, except that here the 

OUTPUT is assigned with the value 0 if the panel is unlocked, or 1 if it is locked. 

 

NOTE 17

 – For clean switching of RGBHV video, the “ seamless switching”  option may be used. The blanking period for the 

transition of the RGB sources may be set in this case, in steps of 25 milliseconds.  

For example, to set for 350ms blanking time (14 steps), send HEX codes 

07 

8E 

A0 

81 

Summary of Contents for VS-81ETH

Page 1: ...Kramer Electronics Ltd USER MANUAL Model VS 81ETH 8x1 Universal CAT 5 Switcher...

Page 2: ...t Configuration Software 14 5 6 3 Configuring the Ethernet Port 17 5 6 4 Using the Web Manager Page 17 5 6 5 Controlling a Machine using the Com Port Redirector 21 5 6 6 Using the Com Port Redirector...

Page 3: ...or Configuration Window 22 Figure 23 Port Setup Window 23 Figure 24 IP Service Setup Dialog Box 24 Figure 25 Port Settings Window 25 Figure 26 Silent Mode Checked in the RDCfg Window 26 Figure 27 Conn...

Page 4: ...ignage The package includes the following items VS 81ETH 8x1 Universal CAT 5 Switcher Power cord and Null modem adapter Windows based Kramer control software2 Windows based Configuration Manager XPort...

Page 5: ...Control the VS 81ETH using the front panel buttons or remotely via RS 485 or RS 232 serial commands transmitted by a touch screen system PC or other serial controller The Kramer Infra Red remote cont...

Page 6: ...Your VS 81ETH 8x1 Universal CAT 5 Switcher 3 Figure 1 VS 81ETH 8x1 Universal CAT 5 Switcher Front and Rear View...

Page 7: ...TE Terminal Block Connects to dry contact switches see section 5 7 8 RS 485 Terminal Block Port Pin G is for Ground connection 1 Pins B and A are for RS 485 9 SETUP Dipswitches SETUP DIPs 1 2 3 4 are...

Page 8: ...onnector to the LINE IN RJ 45 connector on a TP 1202 XGA Line Receiver unit and connect the XGA OUT connector on that TP 120 unit to the acceptor for example a projector 3 Set the dipswitches see sect...

Page 9: ...S 81ETH in the reverse direction do the following2 1 Connect the VGA UXGA computer graphics source to the XGA INPUT of a PT 1103 XGA Line Transmitter and connect4 the LINE OUTPUT on that PT 110 to the...

Page 10: ...ort see section 5 3 5 Connect the power cord3 To transmit the signal from the OUT IN connector to a device connected to the IN OUT connector press the appropriate IN OUT button RS 232 Computer Graphic...

Page 11: ...th RJ 45 connectors Table 3 CAT5 PINOUT EIA TIA 568A EIA TIA 568B PIN Wire Color PIN Wire Color 1 Green White 1 Orange White 2 Green 2 Orange 3 Orange White 3 Green White 4 Blue 4 Blue 5 Blue White 5...

Page 12: ...S 81ETH unit to the Null modem adapter and connect the Null modem adapter with a 9 wire flat cable to the RS 232 DB9 port on your PC To connect a PC to the VS 81ETH unit without using a Null modem ada...

Page 13: ...f the RC 3000 to the A PIN on the RS 485 rear panel port of the VS 81ETH unit Connect the B PIN on the RS 485 rear panel port of the RC 3000 to the B PIN on the RS 485 rear panel port of the VS 81ETH...

Page 14: ...ing controlled when several VS 81ETH units connect to a PC or serial controller Set the Machine on a VS 81ETH unit via SETUP DIPS 1 2 3 and 4 according to Table 4 When using a standalone VS 81ETH unit...

Page 15: ...necting the VS 81ETH Ethernet Port You can connect the Ethernet port either via a crossover cable see section 5 6 1 1 or a straight through cable see section 5 6 1 2 5 6 1 1 Connecting via a Crossover...

Page 16: ...l Area Connection Properties window appears 5 Select Internet Protocol TCP IP and click the Properties Button see Figure 8 Figure 8 Local Area Connection Properties Window 6 Select Use the following I...

Page 17: ...ftware To configure the Ethernet port you have to install and run the XPort configuration software It is important to consider the following points before logging into and configuring the Ethernet por...

Page 18: ...search for devices click the Search icon or select Search Network from the Action menu 5 6 2 3 Assign IP Address Figure 11 shows a device found on the network with the IP addresses assigned at the fac...

Page 19: ...dress do the following 1 Select the device from the main window list 2 Click the Ping icon or select Ping from the Action menu The Ping Device dialog box shows the IP Address of the selected device 3...

Page 20: ...er to access the unit s internal Web pages and configure the unit over the network see section 5 6 4 This is the easiest and preferred method Make sure that the Java 2 Runtime Environment Standard Edi...

Page 21: ...settings Update Settings Press to update settings Channel 1 Disabled When in the Web Manager window 1 Use the menu buttons to navigate to sub pages where you can configure server settings See explana...

Page 22: ...or over one of the fields to display Help messages Figure 16 Server Properties in the Unit Configuration Window Changing the IP address will require you to enter the new IP address in the browser to r...

Page 23: ...w is set1 according to Figure 17 Figure 17 Serial Port Settings Window Make sure that the Local Port in the Dedicated Connection window is set according to Figure 18 Figure 18 Dedicated Connection Win...

Page 24: ...5 1 Installing the Com Port Redirector To install the Com Port Redirector do the following 1 Perform the appropriate step to start the installation If the Com Port Redirector is on a CD ROM insert the...

Page 25: ...or and click Configuration The Com Port Redirector Configuration window appears see Figure 22 Figure 22 Com Port Redirector Configuration Window 6 Click the Com Setup button A Port Setup dialog box ap...

Page 26: ...te After you use the Port Setup dialog box to add or remove Com ports restart your computer 5 6 5 2 Configuring the Com Port Redirector Com Port Redirector is a software utility for network enabling l...

Page 27: ...e Start button in the Windows Taskbar point to Programs point to Lantronix Redirector and click Configuration The Com Port Redirector Configuration window appears see Figure 22 2 Using the Redirect To...

Page 28: ...ng If Timeout Reconnect is disabled the connection attempt fails after this interval and no more attempts are made Force v2 Protocol N A No Net Close If checked prevents the network connection from be...

Page 29: ...e HyperTerminal window opens a pop up window displays Attempting to connect to service If this message is replaced by Successfully redirected to service the connection from the Com Port Redirector to...

Page 30: ...H will route the appropriate IN OUT signal to the OUT IN acceptor4 Figure 27 Connecting a Remote Mechanical Switcher Unit to the VS 81ETH 1 The remote unit can have up to 8 push buttons corresponding...

Page 31: ...the PC using the Null modem adapter provided with the machine recommended as section 5 2 describes 3 Connect the RS 485 terminal block port on the first unit to the RS 485 port on the second VS 81ETH...

Page 32: ...el To prevent changing the settings accidentally or tampering with the unit via the front panel buttons lock1 your VS 81ETH Unlocking releases the protection mechanism To lock the VS 81ETH Press the L...

Page 33: ...re Ethernet IR POWER SOURCE 8 Watts maximum 100 264 VAC 50 60Hz DIMENSIONS 19 inch W 7 inch D 1U H WEIGHT 2 5kg 5 5lbs approx ACCESSORIES Power cord Null modem adapter Windows based control software W...

Page 34: ...e to be set for N5 N0 2nd BYTE Bit 7 Defined as 1 I6 I0 INPUT When switching ie instruction codes 1 and 2 the INPUT 7 bits is set as the input number which is to be switched Similarly if switching is...

Page 35: ...UTPUT byte 32 OR set 0 0 No VIS immediate 1 Input 1 2 External digital sync 3 External analog sync 4 Dynamic sync 5 Inter machine sync 6 Input INPUT byte 7 Output INPUT byte 8 User defined sync 32 RGB...

Page 36: ...t number whose video parameter is to be increased decreased 0 all 0 increase video gain 1 decrease video gain 2 increase contrast 3 decrease contrast 4 increase brightness 5 decrease brightness 6 incr...

Page 37: ...RS 422 controller 14 63 EXTENDED DATA 7 MSBs for INPUT data 7 MSBs for OUTPUT data 20 NOTES on the above table NOTE 1 When the master switcher is reset e g when it is turned on the reset code is sent...

Page 38: ...12 Under normal conditions the machine s present status is saved each time a change is made The power down save auto save may be disabled using this code Note that whenever the machine is turned on t...

Page 39: ...udio gain instruction 22 of output 3 to 681dec 2A9hex you would first send HEX codes 3F 80 85 81 and then send HEX codes 16 83 A9 81 To set the audio gain of output 6 to 10013dec 271Dhex first send HE...

Page 40: ...riginal dated invoice or a copy must be presented as proof of warranty coverage and should be included in any shipment of the product Please also include in any mailing a contact name company address...

Page 41: ...the latest information on our products and a list of Kramer distributors visit our Web site www kramerelectronics com where updates to this user manual may be found We welcome your questions comments...

Reviews: