7
COMMISSIONING
7.1
SAFETY INSTRUCTIONS
WARNING!
This product contains dangerous voltage that when touched can cause electric shock, burns
or death. All contact safety devices must be fitted during operation.
7.2
PREPERATORY INSPECTION
Check that the equipment is free from damage, correctly fitted and that all the ventilation
openings are free from obstacles.
Check that all cable installations, electrical connections and protective earths are correctly
implemented.
Check that the earth wire on the underside of the device is in place.
Check that all contact safety devices and breakers are disconnected.
Check that the rated voltage of the equipment corresponds to the rated voltage of the plant.
7.3
ELECTRIFICATION
7.3.1
DC
Start by connecting the battery by connecting a fuse in the battery circuit, for example. Note that
a connection current occurs when the rectifier modules' output capacitors are being charged.
This could give rise to some spark formation at the point of connection.
After a few seconds, the operator panel display lights up, and after a few more seconds the text
appears on the display. All measurement values are initially reset. The measuring begins after
around 10 seconds. Any alarms are activated when a total of around 30 seconds has passed.
WARNING!
Connection of the battery with wrong polarity may harm the rectifier. At any uncertainty,
do this:
1.
Pull out the rectifier modules.
2.
Engage the battery circuit and check the polarity on the rectifier DC output terminals.
3.
Disengage the battery circuit and restore the rectifier modules.
4.
The continue according to the instructions above
7.3.2
AC
Close the mains breaker on the front of the equipment. The rectifier modules will then start up.
The battery now starts to charge, and if it was in a state of deep discharge, the charging starts
with rated current until the float charging level is reached. Certain types of battery require an