The modules are of the “plug-in” type and can in principle be replaced during operation. For
more information, see the
5.5
VOLTMETER TERMINALS
When measuring the battery voltage you should avoid measuring directly at the battery
terminals due to the risk of arcing in the event of a possible short circuit. Use the short-circuit
protected voltmeter terminal on the front panel instead.
The voltmeter terminal fits a standard 4 mm measuring pin. To avoid
measurement errors, the voltmeter used should have high ohms, 10 Mohm
or better.