WARNING:   Rework   worksheet,  adding   the  space  of   the  adjoining  unconfined  space.  The

combined  spaces  must   have  enough  fresh air  to supply  all  appliances  in  both  spaces.

If  the actual  Btu/Hr  used  is   less  than   the  maximum   Btu/Hr   the  space  can  support, the   space  is   an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                   Btu/Hr
     Gas furnace                                                              Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                        Btu/Hr
     Total                                =                                         Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

                         

Btu/Hr (maximum the space can support)

                          

Btu/Hr (actual amount of Btu/Hr used)

         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building

 (below).

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

 (below) .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
  Vent-free  heater    +       26,000        Btu/Hr
  Total                          =      56,000        Btu/Hr

        

 WARNING:  If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined

as  an  unconfined space or  if  the building  is  of  unusually  tight  construction, provide  adequate

combustion  and  ventilation air by  one of   the  methods  described  in  the  National Fuel  Gas  Code,
ANS  Z223.1, Section  5.3  or  applicable  local  codes.

This  fresh air  would come  from an adjoining  uncon-

fined space.  When  ventilating  to  an  adjoining

unconfined space, you  must  provide  two  perma-

nent  openings: one within 12" of  the  ceiling  and

one  within 12" of  the  floor on  the  wall  connecting

the  two  spaces (see  options 1 and  2, Figure 2).

You  can  also  remove  door  into adjoining  room

(see  option 3, Figure 2). Follow  the  National  Fuel

Gas  Code. NFPA  24/ANS  Z223.1.  Section 5.3,  Air

for  Combustion  and  Ventilation  for required size of

ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors

Provide extra fresh air by using ventilation grills or

ducts. You must provide two permanent openings:

one within 12" of the ceiling and one within 12" of the

floor. Connect these items directly to the outdoors or

spaces open to the outdoors. These spaces include

attics and crawl spaces. Follow the National Fuel

Gas Code, NFPA 54/ANS Z223.1, Section 5.3. Air

for Combustion and Ventilation for required size of

ventilation grills or ducts.

IMPORTANT:Do not provide openings for  inlet

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the

attic will activate the power vent.

Figure  3 -Ventilation  Air  from  Outdoors

Summary of Contents for FMK2501

Page 1: ...s appliance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer World Marketing of America Inc P O Box 192 Rt 22 West Mill Creek PA 17060 KOZY WORLD PHONE NUMBER 814 643 1775 http www worldmkting com R Safety Information Warnings 2 Air for Combustion and Ventilation 4 Installation 6 Operating heater 9 Cleaning Maintenance 10 Tr...

Page 2: ...r ornaments such as pine cones vermiculite or rock wool Using these added items can cause sooting Do not add lava rock around base Rock and debris could fall into the con trol area of heater After servicing always replace screen before op erating heater 7 You must operate this heater with the heater screen in place Make sure heater screen is in place before running heater 8 This heater is designed...

Page 3: ...ge If fireplace or logs are damaged promptly inform dealer where you bought the fireplace from PRODUCT FEATURES SAFETY PILOT This heater has a pilot with an Oxygen Depletion Sensing ODS safety shutoff system The ODS pilot is a required feature for vent free room heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater has a piezo ignitor This sy...

Page 4: ...ning if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms 1 Determine the volume of the space length width height Length Width Height cu ft volume of space Example Space size 20ft length ...

Page 5: ... room unconfined Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr WARNING If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by one of the methods described in th...

Page 6: ...t to vinyl or cloth wall coverings or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may dis color walls IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew See Air for Combustion and Ventilation pages 4 through ...

Page 7: ...mmonly known as wellhead gas CAUTION Only use a new black iron or steel pipe Internally tinned cop per tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur Installation must include an equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach...

Page 8: ...xture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Pressure Testing Heater Gas Connections 1 Open equipment shutoff valve see Figure 8 Figure 9 Checking Gas Joints INSTALLATION Continued CHECKINGGASCONNECTIONS 2 Open gas supply valve 3 Make sure co...

Page 9: ...Turn control knob clockwise to the OFF position 4 Wait five 5 minutes to clear out an y g as Th en smell for gas including near the floor If you smell gas STOP Follow B in the safety information on page 2 If you don t smell gas go to the next step 5 Turn control knob counterclockwise to the PILOT position Press in control knob for five seconds see Figure 11 l Note You may be running this heater fo...

Page 10: ...heater off see To Turn Off Gas to Appliance page 9 l see Troubleshooting pages 11 through 12 CLEANING AND MAINTENANCE WARNING Turn off heater and let cool before cleaning CAUTION You must keep c o n t r o l a r ea s b u r n e r an d circulating air passageways of h eat er c lean In sp ect t h ese ar eas of heater before each u se H ave h eat er insp ec t ed yearly by a qualified service person H e...

Page 11: ... Some burner flame holes may become blocked by debris or rust with no flame present If so turn off heater and let cool Either remove blockage or replace burner Blocked burner flame holes will create soot TROUBLE SHOOTING Note All troubleshooting items are listed in order of operation WARNING Turn off heater and let cool before servicing Only a qualified service person should service and repair hea...

Page 12: ... connected 1 C l e a n b u r n e r s e e C l e a n i n g and Maintenance page 10 or replace burner orifice 2 Contact local propane LP gas company 3 Replace burner orifice 4 Reconnect leads Delayed ignition burner 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact local gas company 2 Clean burner see Cleaning and Maintenance page 10 Burner backfiring during combustion 1 Damaged bu...

Page 13: ... W C 3 W C Inlet Gas Pressure In of water Maximum 14 10 5 Minimum 11 5 Dimensions Inches H W D Stove 38 3 8 26 3 8 14 1 8 Carton 37 29 5 16 15 5 16 Weight lbs Stove 73 73 Shipping 89 89 For purposes of input adjustment GFP2506 GFN2505 carton dimension 41 3 8 29 5 16 17 3 8 FMK2502 FMK2504 GFP2506 FMK2501 FMK2503 GFN2505 ...

Page 14: ... Purchase date l warranty card Usually we will ask you to return the defective part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they can not supply original re placement part s call World Marketing s number on the front page REPLACEMENT PARTS ACCESSORIES Purchase these heater accessories from your local dealer or call KOZY WORLD s Sales Department at 814 6...

Page 15: ...1 5 ILLUSTRATED PARTS BREAKDOWN FMK2501 FMK2502 FMK2503 FMK2504 GFN2505 GFP2506 ...

Page 16: ...E3 Burner LP 1 1 07 EL024 01 Injector NG 1 1 08 EL025 01 Injector LP 1 1 09 EB37000 Outlet Tube Assembly 1 1 10 EB37001 Outlet Tube Assembly 1 1 11 NRV81F1 3 Regulator RV81FI3 NG 1 1 12 NRV81F1 8 Regulator RV81FI8 LP 1 1 13 EB36000 Inlet Tube Assembly 1 1 14 EB36001 Inlet Tube Assembly 1 1 15 EB38000 ODS Inlet Tube Assembly 1 1 16 EB38001 ODS Inlet Tube Assembly 1 1 17 SIT545 218 SIT Thermostat Co...

Page 17: ...1 7 ILLUSTRATED PARTS BREAKDOWN FMK2501 FMK2502 FMK2503 FMK2504 ...

Page 18: ...ket 1 1 7 EL010 01C Upper Decorating Frame 1 1 8 EL011 01 Upper Decorating Wire 1 1 9 EL002 03 01 Upper Mid Louver 1 1 10 EL005 01 Side Reflector 1 1 11 EL007 01 Firebox Floor 1 1 12 EL012 01 Lower Front Panel 1 1 13 EL013 01 Door 1 1 14 224 Brass Knob 1 1 15 EL018 01 Pedestal 1 1 16 EL021 01 Rome Column 2 2 17 EL021 01A Rome Column Decorating Assembly 1 1 18 EL039 01 Leg 1 1 19 EB008 01 Screen 1 ...

Page 19: ...1 9 ILLUSTRATED PARTS BREAKDOWN GFN2505 GFP2506 ...

Page 20: ...de Panel 1 1 9 EL015 06 C Left Right Side Panel 1 1 10 EL015 06 DO Left Right Side Panel 1 1 11 EL019 01 Back Panel 1 1 1 12 EL004 06 Regulator Bracket 1 1 1 13 EL010 01C Upper Decorating Frame 1 1 1 14 EL011 01 Upper Decorating Wire 1 1 1 15 EL002 03 01A Upper Mid Louver 1 1 1 1 1 1 16 EL006 06 Side Reflector 1 1 1 17 EL007 06 Firebox Floor 1 1 1 18 EL012 06A 06B Lower Front Panel 1 1 1 1 1 1 19 ...

Page 21: ...g logs l Fasten decorating logs 1 2 3 onto the correspondent angle iron Figure 4 l Insert the pinhole on the upper part of log 4 into the pin on the left side of log 1 Place the lower part on the flat roof at the left side of log 3 Figure 5 l Insert the pinhole on the upper side of log 5 into the pin on the right side of log 1 Place the lower part on the flat roof at the right side of log 3 Figure...

Page 22: ...A GFN2505 GFP2506 model Guide the operating control hous ing through the bottom hole of rear panel and place it on the mount ing bracket in the door Mounting operating control housing to the mounting bracket with two screw see figure 4 B GFN2505 GFP2506 model Insert operation control housing at the back bottom of stove Use two black screws provided in blower kit Mount blower operation control hous...

Page 23: ...Routing Power Cord Figure 3 B Routing Power Cord Figure 5 Mounting Control Housing WiringDiagram Decal INSTALLING BLOWER ACCESSORY BLOWER ACCESSORY MODEL NFHTX186 MODEL GFN2505 GFP2506 Figure 4 Mounting Control hosing ...

Reviews: