background image

TROUBLESHOOTING 

45

13.0  TROUBLESHOOTING

ATTENTION: Troubleshooting must be performed by a qualified 
technician.

Before proceeding with the steps in the following troubleshooting 
guide, 
•  Verify proper 120VAC power supply to the control module.
•  Verify the control module battery pack and the remote 

control batteries are fresh and installed with correct polarity.

•  Verify all connections between the wire harnesses and the 

system components are proper and positive. 

•  Verify the communication link is established between the 

remote control and the IFC module.

•  Verify inlet pressure meets the recommended inlet pressure. 

If necessary, adjust line pressure regulator.

Issue

Cause

Solution

Pilot will not light

Electrical power interrupted or 
disconnected

Restore electrical power to appliance or use battery back-up.

Wiring disconnection

Ensure batteries are fully charged if using battery back-up as 
power source.
Use wiring schematic

 

to determine that all wiring connections are 

secure and correct.

Gas supply turned off

Check remote shut-off valves from the appliance. Usually there is 
a valve near the main gas line. There may be more than (1) valve 
between the appliance and main gas line.

Pilot will not stay lit

No LP (propane) gas in tank

Check LP (propane tank). Refill if necessary.

Low gas pressure

Consult a plumber or a gas supplier. 
Can be caused by situations such as a bent line, too narrow 
diameter or pipe, or a low line pressure. 

Pilot flame not making contact 
with the flame rectification 
sensor on the pilot assembly

Verify the pilot flame envelopes the top of the flame sensor and 
extends far enough onto burner for ignition.
To adjust pilot flame, turn pilot adjustment screw on the gas valve 
clockwise to decrease flame, and counterclockwise to increase 
flame. 

Pilot adjustment screw not 
sealed

Seal pilot adjustment screw. Do not over-tighten. 

Pilot flame always on, or 
will not extinguish

Control system set to CPI mode

Set control system to IPI mode 

Main burner flame will not 
light

ON/OFF rocker switch in OFF 
position 

Switch rocker switch to ON position.

Gas supply turned off

Check for multiple shut-offs in the supply line. Verify gas supply is 
turned on.

Low gas supply

Consult with plumber or gas supplier. 
Check LP (propane) tank. Refill if necessary. 

Wiring disconnection or 
improper wiring

Check for faulty or incorrect wiring.

Plugged main burner orifice

Remove blockage.

Pilot flame

Verify the pilot flame is properly directed to ignite burner. See pilot 
flame troubleshooting above.

Remote control not working 
properly

Replace batteries.

No call for heat

Verify remote control is powered ON and thermostat operation is 
turned OFF. 

Summary of Contents for SLA-36

Page 1: ...where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit...

Page 2: ......

Page 3: ...safety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong President Dudley Hussong Board Chairman Homeowner...

Page 4: ......

Page 5: ...ON 23 6 1 Gas Conversion sold separately 23 6 2 Gas Line Installation 23 7 0 TERMINATION LOCATIONS 24 7 1 Vertical Vent Cap Termination 24 7 2 Minimum Termination Clearances 25 8 0 VENTING 26 8 1 Appr...

Page 6: ......

Page 7: ...he above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 1 2 3 Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the bu...

Page 8: ...Btu h 4 98 kW 17 000 Btu h 4 98 kW Manifold Pressure High 3 8 WC 0 95 kPa 11 WC 2 74 kPa Manifold Pressure Low 1 1 WC 0 27 kPa 2 9 WC 72 kPa Orifice Size DMS 37 0625 2 2 1 Altitude Adjustment This ap...

Page 9: ...m 81 16 204mm 1513 16 402mm 48 1238mm 61 8 155mm 51 8 130mm 365 8 930mm 7 198mm 2813 16 732mm 39 997mm 435 8 1108mm 48 1238mm 77 8 200mm 18 457mm 513 16 148mm 43 16 107mm 4 121mm TOP FRONT LEFT SIDE R...

Page 10: ...4 Optional Trim Kit Assembly SL36 FTK on page 22 2 4 1 Safety Barrier Installation 1 Center the screen front over the glass frame assembly allowing the screen front s mounting brackets to fit inside t...

Page 11: ...d sheetrock et cetera in this zone Top stand off brackets must be formed and attached prior to positioning fireplace into framed opening 1 Remove and save the 4 screws securing the top stand off heat...

Page 12: ...learances to Combustible Material From appliance top stand offs 0 in 0 mm From appliance left and right side stand offs 0 in 0 mm From appliance back stand offs 0 in 0 mm From appliance bottom stand o...

Page 13: ...nce requirements This fireplace may be elevated off the floor as shown below provided it is properly supported by framing materials and maintains ceiling clearances If masonry is to be used optional p...

Page 14: ...tible material may be used 3 6 Recess Construction WARNING All clearances to venting must be maintained Mounting a television above a fireplace has become a common practice Television surface temperat...

Page 15: ...uired 1 in 25 mm clearance to combustibles must be installed for all horizontal vent runs that pass through interior or exterior walls These wall thimble products may be insulated using unfaced insula...

Page 16: ...etal screws 1 Register cover with screws 4 Sheet rock screws 1 Duct collar 3 Flange nuts 1 Fan assembly 1 Strapping cord 1 Fan housing cover plate 3 Wire nuts 1 Speed control mounting bracket 2 Fan wi...

Page 17: ...allow for sheetrock installation 5 Secure the mounting bracket to framing with the provided 4 sheetrock screws 6 Install the junction box on the wall at desired location The junction box is used to h...

Page 18: ...speed control through the mounting bracket Secure with the mounting nut 4 Secure mounting bracket to the junction box with the 2 screws provided 5 Center the register cover over the fan housing cover...

Page 19: ...fireplace 3 Secure the nailing flanges to the fireplace with screws provided through the slots in nailing flanges 4 Bend perforation on nailing flange until parallel with fireplace face Do not bend to...

Page 20: ...nents To secure material to this area use a silicone sealant that has a 300 F 149 C continuous exposure rating It is acceptable to pre drill holes and to use self tapping screws prior to attach the no...

Page 21: ...E MATERIAL ONLY COMBUSTIBLE MATERIAL ALLOWED COMBUSTIBLE MATERIAL ALLOWED LOWER COVER PANEL COMBUSTIBLE MATERIAL ALLOWED NO SCREWS ABOVE FRAMING BOTTOM 19mm COMBUSTIBLE MATERIAL ALLOWED NON COMBUSTIBL...

Page 22: ...s above and 5 holes below the fireplace opening and 3 holes on each side 2 Align the top and bottom trim panels with the pre drilled holes on the fireplace face Position the flange on the trim panel a...

Page 23: ...ssures in excess of psi 3 5 kPa For test pressures equal to or less than psi 3 5 kPa the appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve A...

Page 24: ...ver 7 12 to 8 12 1 5 0 46 Over 8 12 to 9 12 2 0 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1 22 Over 12 12 to 14 12 5 0 1 52 Over 14 12 to 16 12 6 0 1 83 Ov...

Page 25: ...r inlet to any other appliance 12 in 30 cm 9 in 23 cm K Clearance to mechanical air supply inlet 6 ft 1 83 m 3 ft 91 cm above if within 10 ft 3 m horizontally Massachusetts 10 ft 3 m L Clearance above...

Page 26: ...red 1 in 25 mm clearance to combustibles must be installed for all horizontal vent runs that pass through interior or exterior walls These wall thimble products may be insulated using unfaced insulati...

Page 27: ...5 x 8 Vent Configurations Table 8 1 NG LPG Minimum Maximum Vertical Terminations Minimum 5 x 8 Vertical Length Maximum 5 x 8 Vertical Length 2 ft 610 mm 50 ft 15 2 m 8 5 2 4 x 65 8 Reducer Vent Config...

Page 28: ...5 x 8 Horizontal Run 90 elbow 9 in 229 mm 4 ft 1219 mm Table 8 4 NG Max Vertical Max Horizontal Combination Maximum 5 x 8 Vertical Rise Maximum 5 x 8 Horizontal Run Total 5 x 8 Length 20 ft 6 m 20 ft...

Page 29: ...mm Table 8 6 LPG Max Vertical Max Horizontal Combination Maximum 5 x 8 Vertical Rise Maximum 5 x 8 Horizontal Run Total 5 x 8 Length 20 ft 6 m 20 ft 6 m 40 ft 12 2 m Maximum number of 90 elbows 5 Fig...

Page 30: ...229 mm 3 ft 914 mm Table 8 8 NG LPG Max Vertical Max Horizontal Combination Maximum 4 x 65 8 Vertical Rise Maximum 4 x 65 8 Horizontal Run Total 4 x 65 8 Length 20 ft 6 m 20 ft 6 m 40 ft 12 2 m Maxim...

Page 31: ...d of exterior sealant around outer edge of termination box A placing assembly through the wall pass through in exterior wall Place screws through the four holes B securing it in place 4 Form the 5 8 f...

Page 32: ...s out and up to secure assembly bottom 3 Reinstall component upper heat shield secure with wing nuts re attach component board magnet to upper heat shield 4 Reinstall valve access cover using screws p...

Page 33: ...on 1 Remove glass media from its packaging The glass media may be cleaned prior to installation See section 9 3 3 below 2 Install 10 lbs 4 5 kg of crushed glass onto burner assembly and pilot shield 3...

Page 34: ...the control board out of firebox being careful not to damage sealing gasket lying underneath 9 4 2 Control Board Installation 1 Place control board in firebox aligning holes in the board to the holes...

Page 35: ...t cut or remove the grounding prong from this plug 10 1 Electrical Specifications This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local...

Page 36: ...appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier OPERATING INSTRUCTIONS NOTE When this fireplace is initially lit conde...

Page 37: ...osition for remote control operation of the main burner and fireplace features 11 3 Reset the System for Manual Operation 1 Set the ON OFF rocker switch to OFF position 2 Press the red SWI button on t...

Page 38: ...y 2 seconds move the switch to the ON position The ignition sequence will start again 11 6 1 2 Remote Control ON OFF Key 1 Press the remote control ON OFF key to turn the system OFF 2 After approximat...

Page 39: ...ng pilot option The standing pilot will keep the firebox warm and establish a draft in the vent which allows the main burner to ignite with less air flow disruption When the system is OFF the LCD scre...

Page 40: ...can be set to a desired temperature to control a room s comfort level To activate this function 1 Press the thermostat key The LCD screen will display a temperature bulb graphic the room temperature...

Page 41: ...ode Fan s will operate at previous setting There is no delay in start up or stop time 11 8 9 Accent Light Kit The light intensity can be adjusted through 6 levels 1 Press the mode key to index to the...

Page 42: ...ximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not over tighten 6 Relight pi...

Page 43: ...me but may produce soot on the glass Opening the air shutter will cause a short blue flame that may lift off the burner 12 2 1 1 Venturi Opening Adjustment IMPORTANT Slight adjustments to the venturi...

Page 44: ...gas supply and call a qualified service technician 12 2 2 1 Restrictor Plate Installation 1 Remove the safety barrier and the glass frame assembly 2 Remove 2 screws securing termination access panel...

Page 45: ...gas in tank Check LP propane tank Refill if necessary Low gas pressure Consult a plumber or a gas supplier Can be caused by situations such as a bent line too narrow diameter or pipe or a low line pr...

Page 46: ...to be opened slightly to allow more air into the gas mix Refer to Section 12 2 1 Burner Venturi on page 43 Incorrect vent cap installation Adjust if necessary Vent cap blockage Remove debris if necess...

Page 47: ...e sealed and require no oiling 14 3 Vent System NOTE If the vent air intake system is disassembled for any reason reinstall per instructions provided with installation Section 8 0 Venting on page 26 P...

Page 48: ...ness Assembly 700 653 LPG Burner Orifice 0625 700 625 Pilot Assembly NG 700 596 Conversion Kit NG NCK SL36 SP Pilot Assembly LPG 700 596 1 Conversion Kit LPG LCK SL36 SP Transmitter Remote Control 700...

Page 49: ...ng Manufacturing Co Inc s behalf any additional obligation of liability connected with the unit It is expressly agreed and understood that this warranty is Hussong Manufacturing Co Inc s sole obligati...

Page 50: ......

Page 51: ...efective component s It is expressly agreed and understood that this Lifetime Warranty is Hussong Manufacturing Co Inc s sole obligation and original purchaser s exclusive remedy for defective firepla...

Reviews: