Page 20
TROUBLESHOOTING
FAILURE
CAUSE
REMEDY
Burner creaks
Burner is new (wait)
Chimney is sweating
Poor insulation
Insulate the chimney well
Low exhaust temperature
Increase the minimum power / the boiler temp., it
may be necessary to restore the chimney
Pellet boiler is sweating
Check return flow increase at external control
Heating circuits do not work /
Heating system is slow to heat up
The boiler is on utility water operation
mode
Change operation mode
Hydraulic problem
Contact installer
Altered heating curve
Adjust
Heating circuit pump is defect
Fix it
Air is in the system
Bleed air from system
Pumps run on wrongrotation speed
Fix it
High temperature value on screen
No water in boiler
Fill the system
Circulation pump is not working
Activate / Fix the pump
Air in the system / boiler
Bleed air from system / from boiler
Defective boiler temperature sensor
> Inform customer service