17
GB-088B_f.
-
OUTSIDE TEMP OFF - outside temperature settings above which central
heating circulation is off.
-
FROST PROTECTION: turn on frost protection of the facility.
● HOT WATER TANK:
-
POWER TEMPERATURE: setting coil’s supply temperature.
-
REGULATION: regulation of the temperature in the storage- INSIDE ->
acc. to Tzas/OUTSIDE> acc. to outside thermostat (with OUTSIDE settings
unavailable menu positions: tank temperature, DHW tank program, disinfection,
and manual)
-
UNTIL CALL OFF - turn off the storage circuit.
*
If Hot Water Tank function is off - menu will only show a possibility to turn it
on (‘Turn on’).
● CIRCULATION: switching the circulation 'on' or 'off'
● ROOM TEMP:
-
ROOM TEMP CONTROL: yes -> heating turned off after reaching the set room
temperature.
-
ROOM TEMP HYSTERESIS: room temperature hysteresis with 'ROOM TEMP
CONTROL’ on.
-
SET OUTSIDE ROOM SENSOR: shifting boiler's control to the external
regulator (RP clasp)
*
If OUTSIDE regulator is 'on'- menu will only allow switching to INSIDE regulator
(set INSIDE ROOM SENSOR), after its selection and re-entering MENU items-
select settings of the remaining parameters.
● TURBO:
-
ROOM TEMP HYSTERESIS: room temperature fall triggers this function.
-
HOT WATER TANK: No - turns off hot water for the Turbo function.
-
UNTI CALL OFF - turns off automatic Turbo function.
*
If Turbo function is off - menu will only show a posiibility to turn it on (‘On’).
● PUMP:
-
PUMPS PROTECTION: time to turn the pump on for a short time at a longer
standstill (protection against blocking).
-
AUTOMATIC MODE: yes -> works according to user’s needs / no -> works
constantly.
-
TYPE: pump’s type.
-
REGULATION: constant p. -> constant pressure / variable p. -> variable
pressure.
In the regulation mode (constant p.), the pressure difference produced by
the pump is maintained at the constant set level in terms of performance to
pump’s maximum characteristics. This type of regulation is recommended
for floor heating circulations or older heating systems with pipes of larger
diameters, as well as for all applications with constant characteristics. In the
regulation mode (variable p.) the pressure difference produced by the pump
is maintained at the level of settings changing linearly between 1/2H and H.
Setting pressure differences decreases or increases depending on the flow.