D. Refrigerant Loss

Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and after
manufacture. It is possible that shipping or other damage, or microscopic leaks over a long period, may result
in the need for replenishment of refrigerant charge.

When it has been verified by a Certified EPA Technician

that a refrigerant shortage does exist, the leak must be repaired. Then the unit may be evacuated and
recharged in the field by a Certified EPA Technician only.

CAUTION

E. Relocation

If your Kooltronic Air Conditioner has to be moved to another location by truck, the following precautions
should be taken:

De-mount the air conditioner from the equipment, controller or enclosure.

Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF
KOOLTRONIC AIR CONDITIONERS in this manual under 

Section III. "PRODUCT HANDLING".

Refer to the data on the unit name plate which specifies the type of

refrigerant and the amount of charge in ounces. 

.

IX. Trouble-Shooting

Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to
require only routine maintenance. If your air conditioner should require warranty service, please
contact Kooltronic. If you require service out of warranty, we have compiled a trouble-shooting chart
to assist your service personnel. If additional assistance is required contact Kooltronic at (609) 466-3400

.

Problem

Cause

Solution

Unit does not run.

No Power.

Check Power Source and electrical connection.
Check transformer fuses.
Check unit power connections.

Compressor and condenser

Return temperature is

Normal Operation.

fan do not run.

between Thermostat set

Check return air temperature. 

point and differential

Check sensor connection on Thermostat.

(

75°F to 85°F).

Unit not cooling. (Temperature

Failed Thermostat

Check Thermostat and Contactor wire connections.

difference between return and

or Contactor.

Replace Thermostat or Contactor.

supply air is less than 10°F).

Evaporator Blower is running. 

Low Line Voltage.

Check Nameplate Voltage against supply Voltage.

Compressor and Condenser Blower
do not run. Return temperature is

Failed Compressor.

Check Compressor wire connections.

above set point plus differential (90°F).

Check Compressor overload.
Replace Compressor.

Improper Phasing.

Reverse Power Leads.
Check Phase Monitor.

Failed Low Voltage

Check Output of Low Voltage Transformer.

Transformer.

Summary of Contents for Slimkool K3NA4C4SP28L

Page 1: ...IS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 81 1 19 CDR 20131 SLIMKOOL SERIES K3...

Page 2: ...c model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtual...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...H Cooling BTU H Max Ambient Temperature Min P S I G P S I G Design Pressure Low Side Design Pressure High Side Oz Factory Charge Refrigerant Max Fuse Size HACR Type Circuit Breaker Min Circuit Ampacit...

Page 5: ...n discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperature...

Page 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Page 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 8: ...trical power on 4 Verify that the evaporator blower or fan is running 5 Observe the temperature on the digital display The thermostat must be set a minimum of 10 F below this temperature for the compr...

Page 9: ...m are for reference only and are subject to change WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 1 2 Mounting con t 1 These externally mounted air conditioners have pre installed gaskets...

Page 10: ...3 TYP 27 94 709 6 66 16 8 4 00 101 6 TYP 13 54 343 9 TYP 11 79 299 4 2 75 70 0 TYP 3 96 100 5 1 11 28 1 3 07 78 0 2 64 67 0 10 37 263 3 1 59 40 3 8 76 222 5 DRAIN TUBE 5 83 148 0 1 48 37 5 1 2 2 3 4...

Page 11: ...36 01 Transformer 0932 38 Fuses 2 0916 30 Phase Protector 0694 73 Overload 0694 72 Overload base 0694 74 Filter 9501F SLIMKOOL NEMA 4X model offered with these additional features Stainless Steel Shel...

Page 12: ...or threshold setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and conden...

Page 13: ...lity They are designed to require only routine maintenance If your air conditioner should require warranty service please contact Kooltronic If you require service out of warranty we have compiled a t...

Page 14: ...difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Evaporator Coil...

Page 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: