III. Specific Model Data
Mounting
Kooltronic Air Conditioners have been engineered to be easily installed. To avoid damaging your air
conditioner, please read the following information before installation:
1. Attach plenum to your enclosure with customer supplied hardware (see mounting drawing).
2. Route the power cord and the input and alarm harnesses through the bottom cutout in your enclosure.
It is recommend that a lift truck be used to mount the air conditioner. Hang the air conditioner on the
hooks. Before the lift truck lowers the air conditioner make sure that the hooks are located inside of the
small cutouts on the front panel.
3. Tighten the air conditioner bottom flange to your enclosure with supplied hardware (see mounting
drawing).
4. If the mounting panel of your enclosure is not stiff enough (moment inertia is less than 0.005"
4
) it is
recommended that the three additional supplied screws be used at approximately the middle of the unit
height for proper gasket compression. The screws must be started from inside your enclosure.
5. Attach the supplied drain hose to the drain tubing on the bottom of the air conditioner using the plastic
clamp.
CAUTION
If the air conditioner is mounted to the cabinet door you must be sure
that the door hinges will support the additional weight of the air
conditioner. Also be certain that when the door is opened fully, the
cabinet does not become unbalanced. The actual weight of the unit can
be found in the performance specifications.
Dimensions, inches [metric], are for reference only and are subject to change.
FIGURE 1
MOUNTING PLAN
22.90
[581.6]
1.09
[27.6]
(TYP.)
30.00
[762.0]
0.50
[12.7]
21.98
[558.2]
TYP.
5.72
[145.2]
(TYP.)
1.00
[25.4]
31.20
[792.4]
28.09
[713.5]
61.41
[1559.8]
25.64
[651.2]
2.00
[50.8]
.64
[16.2]
(28) .312 [7.9]
DIA. HOLES
24.17
[613.6]
24.00
[609.6]
5.84
[148.3]
6.00
[152.4]
(TYP.)
PLENUM
26.27
[667.2]
POWER
CORD
CONDENSER
AIR OUT
CONDENSER AIR
IN (3 PLACES)
ENCLOSURE
AIR IN
ENCLOSURE
AIR OUT