IX. Maintenance

Kooltronic Air-Cooled Air Conditioners require no maintainance. In the event of a problem with your air
conditioner, please follow the instructions below.

A. Blowers

The design life of the blowers used in all Kooltronic Air Conditioners is substantially in excess of
20,000 hours. All Kooltronic condenser and evaporator blowers are equipped with automatic-reset
thermal overload protectors.

CAUTION

If field replacement of a blower motor is necessary, most blower assemblies, including the mounting
plate, are readily removable. Each of the blower mounting plates is held to the air conditioner cabinet
structure by screws and nuts. For installation of the replacement blower, electrical connections may
be broken at the terminal block, or power leads may be cut and appropriately spliced together. 

B. Compressor

All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They are
hermetically sealed and charged at the factory, and equipped with automatic-reset thermal overload
protectors.

If the compressor fails, it is strongly recommended that the air conditioner be returned to Kooltronic
for service.

C. Refrigerant Loss

Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and
after manufacture. It is possible that shipping or other damage, or microscopic leaks over a long
period, may result in the need for replenishment of refrigerant charge.

When it has been verified by

a Certified EPA Technician that a refrigerant shortage does exist, the leak must be repaired.
Then the unit may be evacuated and recharged in the field by a Certified EPA Technician only.

CAUTION

D. Relocation

If your Kooltronic Air Conditioner has to be moved to another location by truck, the following
precautions should be taken:

De-mount the air conditioner from the equipment, controller or enclosure.

Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND
SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under 

Section III.

"PRODUCT HANDLING".

Before opening the air conditioner, disconnect all power.

Refer to the data on the unit name plate which specifies the type of

refrigerant and the amount of charge in ounces. 

Summary of Contents for K2A3C30EP62-2

Page 1: ...N BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 60...

Page 2: ...14 XI Warranty 15 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and sha...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Page 5: ...ill be off depending on ambient conditions The crankcase compressor heater allows the unit to start with an ambient temperature of 0 F This unit is also equipped with a Low Temperature Thermostat to p...

Page 6: ...de The compressor and the condenser blower do not run The evaporator blower runs constantly drawing air from the outside through the air filter and the enclosure then discharging air to the outside th...

Page 7: ...installation CAUTION 1 The unit must sit in an upright position at a minimum room temperature of 65 F to allow the system to warm up This is particularly important during winter months 2 Refer to the...

Page 8: ...orator air temperature should be about 12 F higher than the ambient temperature 11 Turn off heating input signal and send input surge signal 12 Verify that the damper is in open horizontal position an...

Page 9: ...d that the three additional supplied screws be used at approximately the middle of the unit height for proper gasket compression The screws must be started from inside your enclosure 5 Attach the supp...

Page 10: ...14 740 2 29 11 739 3 26 27 667 2 12 75 323 9 93 23 6 AMBIENT AIR IN LEFT SIDE FRONT BOTTOM DRAIN LOCATION RIGHT SIDE BACK TOP PLENUM 24 17 613 9 18 20 462 3 ECONOMIZER AIR OUT 2 98 75 7 Drawings and D...

Page 11: ...ponent Replacements K2A3C30EP62R Part Part Number Compressor 0665 57 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Ev...

Page 12: ...LEGEND CR COMPRESSOR RELAY DA DAMPER ACTUATOR RELAY DT DAMPER THERMOSTAT HL HEATER LIMITER HR HEATER RELAY ICR INPUT COOLING REQUEST IHR INPUT HEAT REQUEST IPA INPUT PURGE ALARM ISA INPUT SMOKE ALARM...

Page 13: ...ermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected...

Page 14: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blo...

Page 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: