VI. EP62R A/C Control and Output Alarm Connections

Depending on the customer input signal the air conditioner works in five different modes:

Cooling air conditioner mode

Cooling economizer mode

Heating mode

Purge mode

Smoke alarm mode

The customer could send one of four 24V A/C signals:

1. Cooling air conditioner mode

The compressor, the condenser and the evaporator blower are running, keeping temperature inside of
the enclosure between 75°F and 115°F, depending on internal load and ambient temperature. The
economizer damper is in the closed position.

2. Cooling economizer mode

At ambient temperatures below 55°F. the unit works in the cooling economizer mode. The compressor
and the condenser blower do not run. The evaporator blower runs constantly, drawing air from the
outside through the air filter and the enclosure, then discharging air to the outside through the
economizer damper. The cooling economizer mode keeps temperatures inside the enclosure about
80°F.

3. Heating mode

When in heating mode the unit keeps temperatures inside the enclosure within the range of 55°F and
71°F by activating the electrical heater. 

4. Purge mode

At any ambient temperature the unit works the same way as it does in the cooling economizer mode -
the economizer damper is open and the evaporator blower is running.

5. Smoke alarm mode

In this mode the economizer damper is closed, and the evaporator blower does not run. 

Input signal

Wire color

Common

Red

Cooling request

Black

Heating request

White

Purge alarm

Blue

Smoke alarm

Brown

Summary of Contents for K2A3C30EP62-2

Page 1: ...N BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 60...

Page 2: ...14 XI Warranty 15 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and sha...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Page 5: ...ill be off depending on ambient conditions The crankcase compressor heater allows the unit to start with an ambient temperature of 0 F This unit is also equipped with a Low Temperature Thermostat to p...

Page 6: ...de The compressor and the condenser blower do not run The evaporator blower runs constantly drawing air from the outside through the air filter and the enclosure then discharging air to the outside th...

Page 7: ...installation CAUTION 1 The unit must sit in an upright position at a minimum room temperature of 65 F to allow the system to warm up This is particularly important during winter months 2 Refer to the...

Page 8: ...orator air temperature should be about 12 F higher than the ambient temperature 11 Turn off heating input signal and send input surge signal 12 Verify that the damper is in open horizontal position an...

Page 9: ...d that the three additional supplied screws be used at approximately the middle of the unit height for proper gasket compression The screws must be started from inside your enclosure 5 Attach the supp...

Page 10: ...14 740 2 29 11 739 3 26 27 667 2 12 75 323 9 93 23 6 AMBIENT AIR IN LEFT SIDE FRONT BOTTOM DRAIN LOCATION RIGHT SIDE BACK TOP PLENUM 24 17 613 9 18 20 462 3 ECONOMIZER AIR OUT 2 98 75 7 Drawings and D...

Page 11: ...ponent Replacements K2A3C30EP62R Part Part Number Compressor 0665 57 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Ev...

Page 12: ...LEGEND CR COMPRESSOR RELAY DA DAMPER ACTUATOR RELAY DT DAMPER THERMOSTAT HL HEATER LIMITER HR HEATER RELAY ICR INPUT COOLING REQUEST IHR INPUT HEAT REQUEST IPA INPUT PURGE ALARM ISA INPUT SMOKE ALARM...

Page 13: ...ermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected...

Page 14: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blo...

Page 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: