VIII. Maintenance

Kooltronic Air-Cooled Air Conditioners require no maintainance. In the event of a problem with your air
conditioner, please follow the instructions below.

A. Blowers

The design life of the blowers used in all Kooltronic Air Conditioners is substantially in excess of
20,000 hours. All Kooltronic condenser and evaporator blowers are equipped with automatic-reset
thermal overload protectors.

CAUTION

If field replacement of a blower motor is necessary, most blower assemblies, including the mounting
plate, are readily removable. Each of the blower mounting plates is held to the air conditioner cabinet
structure by screws and nuts. For installation of the replacement blower, electrical connections may
be broken at the terminal block, or power leads may be cut and appropriately spliced together. 

B. Compressor

All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They are
hermetically sealed and charged at the factory, and equipped with automatic-reset thermal overload
protectors.

If the compressor fails, it is strongly recommended that the air conditioner be returned to Kooltronic
for service.

C. Refrigerant Loss

Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and
after manufacture. It is possible that shipping or other damage, or microscopic leaks over a long
period, may result in the need for replenishment of refrigerant charge.

When it has been verified by

a Certified EPA Technician that a refrigerant shortage does exist, the leak must be repaired.
Then the unit may be evacuated and recharged in the field by a Certified EPA Technician only.

CAUTION

D. Relocation

If your Kooltronic Air Conditioner has to be moved to another location by truck, the following
precautions should be taken:

De-mount the air conditioner from the equipment, controller or enclosure.

Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND
SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under 

Section III.

"PRODUCT HANDLING".

Before opening the air conditioner, disconnect all power.

Refer to the data on the unit name plate which specifies the type of

refrigerant and the amount of charge in ounces. 

10

Summary of Contents for C20A0647

Page 1: ...OOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 39 8 21 CDR 20346 INTREPID EP56 SERIES K2A4C30EP56TR BR Find additional informati...

Page 2: ...onic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of...

Page 3: ...rior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection t...

Page 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Page 5: ...where it absorbs the heat and is then discharged to the environment The unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing and must not be set below the f...

Page 6: ...the thermostat to its minimum setting turn it counterclockwise The compressor should start On units equipped with a short cycle protector the compressor will have a delayed start of 6 minutes from the...

Page 7: ...in hose to the drain tubing on the bottom of the air conditioner using the plastic clamp CAUTION 7 If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will supp...

Page 8: ...0 POWER CORD 1 1 2 EP56B EP56T 3 4 EP56T EP56B 3 4 57 04 1448 7 DRAIN Drawings and Dimensions EP56 SERIES Dimensions inches metric are for reference only and are subject to change FILTERED CONDENSER...

Page 9: ...ing BTU H Ambient Temp F Max Min Volts Hz Cooling Amps Heating Amps Approx Weight lbs K2A3C30EP56TR K2A3C30EP56BR K2A6C30EP56TR K2A6C30EP56BR 30000 30000 30000 24000 30000 24000 26000 26000 28000 2200...

Page 10: ...mal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected t...

Page 11: ...ssor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Cle...

Page 12: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: