VII. Specific Model Data
Mounting
Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your Air
Conditioner, please read the following information before installation:
1.
Loosen two screws on the bottom of the unit.
2.
See Figure 1 for proper M/TAB orientation.Place the M/TAB flush against the outside of the
enclosure to locate cutouts and mounting holes.
3.
Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (
1/
4
-20 screws/nuts/washers). NOTE: Make sure the screws are inserted with heads
on M/TAB side. Tighten nuts securely.
4.
Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by
sliding the slots located on the front panel on the hooks of the M/TAB.
5.
Tighten two screws on the bottom of the unit and seal the unit against the enclosure.
6.
Attach overflow drain hose supplied to the drain exit in bottom of the unit.
CAUTION
If the Air Conditioner is mounted to the cabinet door you must be sure
that the door hinges will support the additional weight of the Air
Conditioner. Also be certain that when the door is opened fully, the
cabinet does not become unbalanced. The actual weight of the unit can
be found in the Technical Data on page 9.
7
Dimensions (inches) are for reference only and are subject to change.
MOUNTING PLAN
Warm Air Return
From Enclosure
Cool Air Supply
To Enclosure
Ambient Air In
Heated Ambient
Air Out
1.00
[25.4]
2.20
[55.9]
6.75
[171.5]
17.50
[444.5]
6.75
[171.5]
0.56
[14.2]
10.25
[260.4]
11.25
[285.8]
7.00
[177.8]
6.25
[158.8]
0.44
[11.2]
(6) .281 [7.1]
DIA. HOLES
9.31
[236.5]
0.50
[12.7]
1
2
FIGURE 1
RP17 SERIES
WARM AIR RETURN FROM
ENCLOSURE
COOL AIR OUTLET
TO ENCLOSURE
1
2