Kooltronic Air Conditioners are required when the equipment operating temperature must
be kept near or lower than the ambient room temperature, and/or the cabinet must be
sealed from dust, fumes, oil, corrosives and other contaminants. This Air Conditioner
utilizes a "Closed-Loop Cooling System" to ensure optimum performance of the installed
components.
Closed-Loop cooling seals the electronics enclosure from hostile elements in the
environment. Two separate circulation systems are employed. The internal system cools
and dehumidifies the air inside the cabinet, totally isolating the sensitive electronics and
other components from the environment. The external system uses circulating ambient
air to discharge the heat removed from the electronics.The heat is dissipated from the
enclosure by means of the vapor compression refrigeration cycle. This takes place in a
hermetically-sealed refrigeration system, utilizing an air-cooled condenser heat exchanger.
The warm air inside the enclosure is drawn through the evaporator coil where it is cooled,
dehumidified and returned.
Any enclosure moisture accumulated on the evaporator coil is collected and evaporated
in the condensate evaporator tray and released to the ambient air by the condenser blower.
If latent heat exceeds 25% of the total cooling capacity excess condensate is released to
the ambient through the drain tube.
The heat removed through the evaporator coil is transferred by the compressed refrigerant
to the condenser coil. Ambient air is then passed through the condenser coil, where it
absorbs the heat and is then discharged to the environment.
The unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil
from freezing and must not be set below factory setting of 75°F (16°F differential). If
necessary the thermostat may be adjusted to increase the temperature within the
cabinet. Unlike thermostats that are commonly found in household air conditioners
that control the room temperature, the thermostat found on the RP17 monitors the
return air from the enclosure to prevent the evaporator from freezing. In conditions of
low ambient temperature and low enclosure load, the thermostat regulates the return
air temperature from 75°F to 91°F. If the unit is equipped with an optional non-
adjustable high temperature alarm, it will activate when the return air teperature
reaches 130°F.

CONDENSER OUTLET

(Heated Ambient Air Out)

CONDENSER HEAT

EXCHANGER

REFRIGERANT

FILTER DRIER

COMPRESSOR

EVAPORATOR

HEAT EXCHANGER

COOL AIR TO

ENCLOSURE

ACCUMULATOR

CONDENSER

AIR INLET

(Ambient Air In)

HEATED AIR FROM

ENCLOSURE

M/TAB

CONDENSATE

EVAPORATOR TRAY

V. Principles of Operation

Summary of Contents for Advantage K2A4C1RP17R

Page 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 35 1 19 CDR 20131 ADVANT...

Page 2: ...e of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all size...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Page 5: ...by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator coil is tra...

Page 6: ...layed start of 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the system...

Page 7: ...n the hooks of the M TAB 5 Tighten two screws on the bottom of the unit and seal the unit against the enclosure 6 Attach overflow drain hose supplied to the drain exit in bottom of the unit CAUTION If...

Page 8: ...4 277 9 9 54 242 3 7 60 193 0 1 56 39 6 12 35 313 7 1 00 25 4 DIA HOLE 6 18 157 0 2 21 56 1 1 3 4 2 Drawings and Dimensions RP17 SERIES 8 Dimensions inches are for reference only and are subject to ch...

Page 9: ...ntrol Switch Low Temperature Control Thermostat NEMA 12 3R Ratings Maintained UL CUL Recognized Technical Data RP17 Series KA4C1RP17R 1000 125 0 115 100 60 50 7 0 7 5 64 K2A4C1RP17R 1000 125 0 230 200...

Page 10: ...and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable...

Page 11: ...ass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect re...

Page 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: