110013961AA
date of change: 18.08.2008
page: 14/19
Group
]
InP
(parameter concerning measurement inlets)
Par.
Description
Range
Def.
SEnS
Sensor type
Ptc - ntc
Ptc
OFS1
Calibration sensor Pr1 (cell)
-30 ÷ 30
°C/°F
-1.5
OFS2
Calibration sensor Pr2 (evaporator)
-30 ÷ 30
°C/°F
-1.5
Pr 2
Sensor exists Pr2 (evaporator)
On - OFF
On
Unit
Unit of measurement
°C - °F
°C
dP
Decimal point
On - OFF
On
FiL
Measurement filter
OFF ÷ 20.0
sec
2.0
diSP
Variable which is normally indicated in display:
OFF=display off
Pr1=measurement sensor Pr1
Pr2=measurement sensor Pr2
SP= active setpoint
OFF - Pr1
Pr2 - SP
Pr1
Group
]
rEG
(parameter of temperature control)
[refers to Pr1]
Par.
Description
Range
Def.
CooL
Cooling
nr
Cooling
Neutral zone
Heating
HSEt
Hysteresis for compressor OUT
Only visible, if control mode is Func=„HEAT“ or „CooL“
If control mode is FunC = nr, then it is hidden
0 ÷ 30
°C/°F
2.0
2.0
----
tonE
On-time outlet OUT with defective sensor Pr1
OFF ÷ 99.59
min.sec
OFF
OFF
----
toFE
Off-time outlet OUT with defective sensor Pr1
OFF ÷ 99.59
min.sec
OFF
OFF
----
tCC
Continuous operation
OFF ÷ 99.59
hrs.min
OFF
OFF
----
Func
Operating mode outlet OUT (control mode)
HEAt= heating
CooL= cooling
nr= neutral zone
HEAt – CooL
nr
CooL
CooL
nr
Parameter for realization of control „neutral zone”
only visible, if control mode is Func = nr
HI
Limit value at high temperature
(relative on SP)
(switching-on „cooling“)
0 ÷ 30
°C/°F
2.0
----
2.0
LO
Limit value at low temperature
(relative on SP)
(switching-on „heating“)
0 ÷ 30
°C/°F
2.0
----
2.0
SPL
Limit temperature switching-on „heating“ depending on
setpoint
(if the setpoint is under the current value SPL, then no
„heating“ but „neutral zone“ or „cooling“)
SPLL ÷ SPHL
-15
----
-15