110013961AA
date of change: 18.08.2008
page: 19/19
Group
]
PAn
(parameter of keyboard configuration)
Par.
Description
Range
Def.
Fbd
Operating mode button DOWN
OFF= no function
1= control auxiliary outlet
2= manual defrost cycle
3= activate setpoint
4= switching-on/-off (stand-by)
indication of
-
Operating hours
-
Service hours
OFF / 1 / 2 / 3 / 4
0…9999 h
0…9999 h
OFF
USrb
Operating mode button U
4= switching on/-off (stand-by)
OFF / 1 / 2 / 3 / 4
4
PASS
Password for access to operating parameter
OFF ÷ 9999
213
tSEr Service-hours counter
If the programmed value is exceeded, „SEr“ will be
indicated in the display for approx. 5 seconds
This will be indicated with every switching-on of the
FR4, as long as the current value is > than the pro-
grammed value
OFF ÷ 9999
2000
rSEc Reset service-hours counter
By enter of „password „–181“ (minus 181)“ the ser-
vice-hours counter is reset to „0“.
If you enter the wrong password, the display returns
to normal indication and the current value of the ser-
vice-hours counter is conserved.
REMARK:
The password „-181“ is hard-coded.
-1999 ÷ 9999
0
a02
18.08.08 K. Best OFS1 And OFS2: Def. has been 0.0
Fbd: def. “OFF” inserted
110013961AA-a02
a01
30.11.07 K. Best PtC has been 2, Fd has been 1,
tSEr has been 1000
110013961AA-a01
version
date
name
comment
file