Figure 29 for the wall/panel cutout dimensions or to the corresponding mechanical drawings for your
FusionView on our web site www.kontron.com.
3.
The system must be properly powered down and disconnected from the power source and peripherals.
4.
The wall/panel where you intend to install the system must be accessible from both sides (front as well as rear).
The material strength and stiffness must be sufficient to hold the FusionView unit.
5.
Insert the system into the wall/panel cutout from the front.
6.
In order to ensure the protection class IP65 on the front side in the installed condition, the contact surface with
the gasket must be clean and flush.
7.
Hook the mounting clamps with screws (Table 13) from the rear side of the panel into the corresponding pairs of
slots as shown in Figure 26.
8.
The system must be attached firmly by tightening the screws . Always tighten screws in pairs on opposite sides
of the front panel. Repeat the tightening sequence two times and increase the torque from 0.4 to 0.7 Nm.