background image

konner-sohnen.com   

|

   

4

BEST

BEST

(front installation)

RIGHT

RIGHT

(vertical installation)

RIGHT

RIGHT

(back installation)

WRONG

WRONG

(inverted installation)

SCHEMATIC DIAGRAM OF CORRECT  

INSTALLATION METHOD

5

ENVIRONMENTAL REQUIREMENTS FOR USE

6

Name

Requirements

Operating temperature

-20 То +45°С, the average value for 24 hours 

 

shall not 35°С;

Operating humidity

The average humidity under the +40°С conditions shall not 

exceed 50% without condensation;

Altitude

Lower than 2000 meters and, if higher than 2000 meters, 

reduce its rated value for use:

Vibration and gas

There shall bе no stroпg vibration or shock апd nо harmful 

gases to corrode the metals аnd to damage the iпsulation 

within the environment of its use;

Surrounding material

There shall bе nо serious dust, conductive particles or 

explosive hazardous substances

Class of pollution

Class III

ІР rating

IP20

Storage requirements

То bе stored under -З0 То 70°С and in а dry, non-corrosive 

and saline environment and the longest period of storage 

shall bе 1 year

Summary of Contents for KS ATS 4/100HD

Page 1: ...Please read this manual carefully before use Manual KS ATS 4 100HD KS ATS 4 100HD O AUTOMATIC TRANSFER SWITCH ATS EN...

Page 2: ...ections must be carried out by a certified electrician in accordance with all electrical codes and regulations Do not operate the product with your feet in the water on wet or damp soil Do not touch l...

Page 3: ...4 100HD O Consumption 18W 18W Operating voltage 230 V 400 V 230 V 400 V Power 230 V kVA cosPhi 1 0 23 W 23 W Current max 230 V 100 A 100 A Power 400 V kVA cosPhi 0 8 55 W 55 W Current max 400 V 100A...

Page 4: ...f copper bar Ue AC440V Use category Rated operating current of copper bar 100 Rated making capacity 10 10 times the rated current Rated breaking capacity 8le 8 times the rated current Rated limit shor...

Page 5: ...itions shall not exceed 50 without condensation Altitude Lower than 2000 meters and if higher than 2000 meters reduce its rated value for use Vibration and gas There shall b no stro g vibration or sho...

Page 6: ...smaller than the data listed in thetable above which listed for reference only Current range lnstallation data Maximum size of the b d Other detailed dimensions of switch LF WF HF LM WM HM A B C D E F...

Page 7: ...ctive control when closed See S n 0iagram for delails 202 Extemal passive control signal input common terminal Passive control signals 203 Line is switched n when closed with 202 204 Line 0 is switche...

Page 8: ...ndicator light for the 125 to 250 switches is lit up which stands for that the key switch or the button is in the ON position type switch 100 has no LED indicator equipped NOTE 3 4 5 6 Line control re...

Page 9: ...konner sohnen com 8 INTERNAL PRINCIPLE DIAGRAM 10 The above drawing is only a shematic diagram of its working principle which does not represent the number of its internal components NOTE...

Page 10: ...f the product Normal wear and tear of the product remaining life Malfunctions arising from the use of the product for business related purposes The warranty card that is not filled out or does not bea...

Page 11: ...konner sohnen com 10 ANNEX Fig 1 ONE PHASE ATS ONE PHASE ATS ATS CONNECTION TERMINAL ATS CONNECTION TERMINAL...

Page 12: ...konner sohnen com 11 ANNEX Fig 2 ATS CONNECTION TERMINAL ATS CONNECTION TERMINAL THREE PHASE ATS THREE PHASE ATS...

Page 13: ...p de Kundendienst technische Fragen Kundendienst technische Fragen und Unterst tzung und Unterst tzung support dimaxgroup de Garantie Reparatur und Service Garantie Reparatur und Service service dimax...

Reviews: