8
Parameter detail setup
94
© Copyright Reserved KONICS Co., Ltd.
8.4.7
Response Wait Time (Communication response wait time)
To prevent possible error due to communicating with low speed Master (PC, PLC, etc), set
communication response wait time.
If you set too short communication response wait time, communication error may occur in Master.
Set range: 5 to 99 (unit: ms)
Factory default: 20ms
8.4.8
Protocol (Communication protocol)
It supports Modbus RTU(Remote Terminal Uint) as communication protocol.
(Data Length: 8bit, Data interval: 24bits or less,Error Detection: CRC-16)
Set range: Modbus RTU
Factory default: Modbus RTU
8.4.9
RS485 Com Write (RS485 communication write)
Set whether changing the set value of KRN100 parameter by RS485 communication.
To read the set value of each parameter is available regardless of the communication write
enable/disable setting.
Set range : Enable
↔
Disable
Factory default : Enable
Summary of Contents for krn100
Page 1: ... Copyright Reserved KONICS Co Ltd i USER MANUAL ...
Page 2: ...ii Copyright Reserved KONICS Co Ltd ...
Page 12: ...Table of Contents xii Copyright Reserved KONICS Co Ltd ...
Page 26: ...2 Specification 26 Copyright Reserved KONICS Co Ltd ...
Page 28: ...3 Dimensions 28 Copyright Reserved KONICS Co Ltd ...
Page 32: ...4 Connection 32 Copyright Reserved KONICS Co Ltd ...
Page 45: ...7 Operation Copyright Reserved KONICS Co Ltd 45 7 Operation ...
Page 52: ...7 Operation 52 Copyright Reserved KONICS Co Ltd 7 3 2 Parameter ...
Page 54: ...7 Operation 54 Copyright Reserved KONICS Co Ltd ...
Page 144: ...9 DAQMaster 144 Copyright Reserved KONICS Co Ltd ...
Page 150: ...10 Maintenance 150 Copyright Reserved KONICS Co Ltd ...
Page 153: ...11 Troubleshooting Copyright Reserved KONICS Co Ltd 153 ...
Page 154: ......