8
Parameter detail setup
84
© Copyright Reserved KONICS Co., Ltd.
8.2.11
Alarm-
□
Status(Relay and TR output method)
Set alarm output method (Normally Open, Normally Closed) of each alarm output channel from
the set alarm output card in Select Alarm Card (Select alarm output card).
You can use alarm output as relay output or TR output by inserting the desired alarm output
card(Relay output: KRN-AR4, TR output: KRN-AT6).
Set
value
Description
Alarm
occurrence
Alarm output
Relay
TR
N.O.
Normally
Open
In normal status it is open.
If alarm occurs, it is closed.
OFF
Contact Open
TR OFF
ON
Contact Close TR ON
N.C.
Normally
Closed
In normal status it is closed.
If alarm occurs, it is open.
OFF
Contact Close TR ON
ON
Contact Open
TR OFF
This function displays as Alarm-
□
Status and it is connected Relay or TR Type’s output card
information. One card for relay has 4 outputs(Alarm-1 Status to Alarm-4 Status), for TR has 6
outputs (Alarm-1 Status to Alarm 6 Status).
Relay output card(KRN-AR4) is connectable up to 3, and TR output card (KRN-AT6) is
connectable up to 2 at Slot7 to 10.
Alarm output turns ON or OFF by total 4 alarm conditions and relay, TR output are able to output
by max. 48 alarm conditions. However, every relay output and TR output condition is OR
operation (Among several alarm conditions connected one alarm output, even one alarm
condition is met, output must turn ON.).
Set range: N.O.
↔
N.C.
Factory default: N.O.
REALY and TR type output is basically fixed as Normally Opened method and H/W when power
is ON.
Therefore, KRN100 takes booting time max. 20sec and maintains Normally open status. In case
of RUN mode after booting, it maintains use-defined output type; Normally Open or Normally
Closed.
Summary of Contents for krn100
Page 1: ... Copyright Reserved KONICS Co Ltd i USER MANUAL ...
Page 2: ...ii Copyright Reserved KONICS Co Ltd ...
Page 12: ...Table of Contents xii Copyright Reserved KONICS Co Ltd ...
Page 26: ...2 Specification 26 Copyright Reserved KONICS Co Ltd ...
Page 28: ...3 Dimensions 28 Copyright Reserved KONICS Co Ltd ...
Page 32: ...4 Connection 32 Copyright Reserved KONICS Co Ltd ...
Page 45: ...7 Operation Copyright Reserved KONICS Co Ltd 45 7 Operation ...
Page 52: ...7 Operation 52 Copyright Reserved KONICS Co Ltd 7 3 2 Parameter ...
Page 54: ...7 Operation 54 Copyright Reserved KONICS Co Ltd ...
Page 144: ...9 DAQMaster 144 Copyright Reserved KONICS Co Ltd ...
Page 150: ...10 Maintenance 150 Copyright Reserved KONICS Co Ltd ...
Page 153: ...11 Troubleshooting Copyright Reserved KONICS Co Ltd 153 ...
Page 154: ......