1. EQUIPMENT SERIES
KLASIK R
Ventilation units with rotary heat exchanger. Tempera-
ture efficiency up to 85%.
KLASIK P
Ventilation units with plate heat exchanger. Tempera-
ture efficiency up to 70%.
KLASIK CF
Ventilation units with counter flow plate heat exchang-
er. Temperature efficiency up to 92%.
KLASIK S
Air supply or exhaust units.
KLASIK RA
Ventilation units with liquid cupled heat exchanger.
Temperature efficiency up to 63%.
KLASIK Hg, RA Hg, P Hg
Ventilation equipment for hygienic purposes.
S Hg, RA Hg, P Hg series of ventilation equipment for
operation in clean rooms are subject to more stringent
sanitary requirements. Inner surfaces of S Hg, RA
Hg, P Hg series equipment are straight-lined, have no
thresholds and bumps to harbour contamination and
pathogens. All connections are additionally sealed with
dust-tight sealant.
The bottom of these devices (and, as the case may
be, all internal walls) are made of stainless steel, which
allows to clean the interior surface with disinfectants.
2. CONSTRUCTION
Walls in KLASIK units are made of two galvanized steel
sheets filled with heat and sound insulating non-com-
bustible material. Mineral wool is used for thermal in-
sulation (λ = 0.036 W/mK; ρ = 32 kg/m
3
). Ventilation
units are available with 45 mm or 50 mm thick walls,
and tin sheets coated with zinc (275 g/m
2
). Ventilation
unit walls can be:
• Galvanized sheet steel – a standard option
• Galvanized sheet steel, external/internal spray
painted powder
• Stainless steel plate on the inside (the whole inside
or just the bottom). In this case, the ventilation unit
is designed for the ventilation of clean premises.
The housing design reduces the «heat bridge» effect.
All ventilation unit doors are sealed with a special
profile rubber gasket with an air gap. It is attached
mechanically, and additionally bonded with hygienic
glue. This leak-proof design is leak-proof and durable.
Based on the standard CEN preEN 1886, the housing
of KLASIK units meets the tightness class A and its
total heat transfer is T3 class.
Easy to use door locks and handles ensure safe unit
maintenance.