2.9. Cooler section
Water air coolers
As a standard, are used with aluminium fins and cop-
per pipes.
Maximum pressure – 21 bars.
Air cooler section is equipped with a drain outlet and
a siphon.
Direct evaporation air coolers
Normally are used with aluminium fins and copper
pipes.
Maximum pressure – 42 bars.
The cooler section is equipped with a drain outlet and
a siphon. Direct evaporation air cooler capacity can be
divided into steps.
The cooler along with the drainage outlet and the drip
tray can be removed from the inspection side, by dis-
connecting the pipes and unscrewing the panel mount-
ing screws. All coolers in the devices are mounted on
rails, so they are easy to remove.
KLASIK
size
B
H
b
h
mm
1
1015
555
700
300
2
1155
655
900
400
3
1305
710
1000
500
4
1505
810
1200
600
5
1745
955
1400
700
6
1905
1010
1600
800
7
2140
1130
1800
900
8
2310
1265
2000
1000
9
2310
1490
2000
1200
10
2310
1570
2000
1300
11
2590
1650
2200
1400
12
2890
1830
2500
1600
B
b
h
H
For ventilation units operated outdoors when the ambient air temperature t
amb
< 0°C,
it is necessary to use water-ethylene glycol mixture to prevent freezing of water
and damage to the heat exchanger
When the air flow exceeds 2.5 m/s, the drop tray is recommended!