3.4. Electrical installation
Installation works may be performed only by duly qualified personnel. The following requirements must be fulfilled
during installation.
It is recommended to lay control circuit cables separately from power cables or to
use shielded cables. In this case, the cable shielding must be grounded!
After unit parts have been connected together, the connecting cables and wires of the sections of the unit are
connected.
Connector connection is performed strictly according to numeration given in wiring
diagram, or adequate markings (see unit electric scheme).
When disconnecting sections of the unit, do not pull connecting wires and cables!
Electric power supply (400 V AC; 50 Hz voltage) is connected to the main switch, which is envisaged in the heat
exchanger (middle) section of the air handling unit. Prior to connecting to the power supply, the main switch must
be installed near the unit in the intended place or directly on its wall. It is necessary to connect earthing!
All units must be connected through circuit breaker with 300 mA current leakage
protection (type B or B+).
Earth must be installed according EN61557, BS 7671.
When the unit is equipped with an electric heater, every switch of the heater section must be additionally pow-
ered.
Power supply cable for the unit and an electric heater is selected according to the maximum current strength
indicated in the technical data sheet.
When the ventilation unit is equipped with integrated automatics, external connection terminals, corresponding
to the ones located in a controller box, are foreseen inside the unit. All external automation components must
be connected to these terminals (follow the “Electrical Installation and Operating Instructions” provided with the
automation).
If the device is not equipped with factory installed control automation, the company
which installed the automation is responsible for proper operation of the device as
well as safety guards.