3.5. Connection of sections
Depending on unit dimensions, separate sections may
be interconnected with external tightening elements
(see Fig. A.) or internal tightening corners (see Fig. B),
using the supplied screws. Sealing gaskets must be at-
tached on connection points before joining the sections
(supplied with the unit). Screws must be tightened so
that the gasket is fully compressed and distance be-
tween the sections does not exceed 2–3 mm. In case
of the outdoor installed unit, connection between the
sections must be additionally sealed with silicone or
other sealant.
Išoriniai suveržimo elementai
Klijuojama tarpinė
External tightening elements
Adhesive gasket
Fig. A
Vidiniai suveržimo kampai
Klijuojama
tarpinė
Adhesive
gasket
Internal tightening
corners
Fig. B