Graphic Operator Terminal /
INSTALLATION
2. Place the panel cut out where the graphic operator terminal is to be situated, draw along the
outer sides of the holes and cut according to the markings.
3. Secure the graphic operator terminal in position using all the fastening holes and the provided
brackets and screws:
4. Connect the cables in the specified order.
A.
CAUTION!
Ensure that the graphic operator terminal and the controller system have the
same electrical grounding (reference voltage level), otherwise errors in communication
may occur.
B. Use an M5 screw and a grounding conductor (as short as possible) with a cross-section
of minimum 2.5 mm
2
.
C.
CAUTION!
Use only shielded communication cables. Separate high voltage cables from
signal and supply cables.
D.
CAUTION!
The graphic operator terminal must be brought to ambient temperature
before it is started. If condensation forms, ensure that the graphic operator terminal is dry
before connecting it to the power outlet. Ensure that the voltage and polarity of the power
source is correct.
8