background image

7

Owner’s Manual

6SS12BEA2ACA0 / 6SS24BGA2ACA0

SELF-DIAGNOSTIC CODES

Alarm Display

Problem

Cause

Corrective Action

Frost prevention 

sensor and Abnormal 

temperature sensor 

value 

a.  Indoor heat exchanger 

temperature too low

b.  TH3 temperature sensor has a 

loose or broken connection

a.  Do not use the air conditioner 

if ambient temperature is 

lower than 64°F (18°C)

b.  Contact a qualified service 

technician

Refrigerant high 

pressure switch

a.  Blocked air filter

b.  Ambient temperature is too high

c.  Cooling pump is not operating 

normally

d.  Power is not supplied to 

outdoor unit

a.  Clean air filter

b.  Do not use the air 

conditioner if ambient 

temperature is higher than 

125.6°F (52°C)

c.  Check circulating pump is 

operating normally. Check 

the cooling water line 

between indoor and outdoor 

unit is not pinched.

d.  Connect power cord 

between indoor unit and 

outdoor unit Contact service 

center if problem persists

Abnormal temperature 

sensor value

TH1 outlet temperature sensor 

has a loose or broken connection

Contact service center

Abnormal temperature 

sensor value

TH2 inlet temperature sensor has 

a loose or broken connection

Contact service center

Compressor 

overloaded

a.  Ambient temperature is too high

b.  Unstable voltage supply

c.  Defective compressor

a.  Do not use the air conditioner 

if ambient temperature is 

higher than 125.6°F (52°C)

b.  Contact service center if 

problem persists.

c.  Replace compressor

Condensate water 

level alarm

Drain of condensate water is not 

working well.

a.  Cycle power

b.  Check condensate pump to 

ensure operation.

c.  Check condensate hose for 

pinch or kink. 

7

6SS12BEA2ACA0 / 6SS24BGA2ACA0

Owner’s Manual

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

6SS12BEA2ACA0 / 6SS24BGA2ACA0

Owner’s Manual

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

6SS12BEA2ACA0 / 6SS24BGA2ACA0

Owner’s Manual

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

6SS12BEA2ACA0 / 6SS24BGA2ACA0

Owner’s Manual

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

6SS12BEA2ACA0 / 6SS24BGA2ACA0

Owner’s Manual

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

6SS12BEA2ACA0 / 6SS24BGA2ACA0

Owner’s Manual

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

7

WSC-4000 / WSC-6000

Owner’s manual

Frost prevention

sensor and

Abnormal

temperature

sensor value

Refrigerant high

pressure switch

Abnormal

temperature

sensor value

Abnormal

temperature

sensor value

Compressor

overloaded

Condensate

water level

alarm

a. Indoor heat

    exchanger

    temperature too low
b. TH3 temperature

    sensor has a loose or

    broken connection
a. Blocked air filter
b. Ambient temperature

    is too high

c. Cooling pump is

    not operate normally

d. Power is not supplied

    to outdoor unit

TH1 outlet temperature

sersor has a loose or

broken connection

TH2 inlet temperature

sensor has a loose or

broken connection

Drain of condensate

water is not working

well.

a. Ambient temperature

    is too high

b. Unstable voltage

    supply
c. Defective compressor

a. Do not use the air

    conditioner if ambient

    temperature is lower than

    18°C (64°F)
b. Contact a qualified

    service agent
a. Clean air filter
b. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)

c. Check Cooling pump

    is operating normally.

    Check the cooling water

    line between indoor and

    outdoor unit is folded.

d. Connect power cord

     between indoor unit and

     outdoor unit

Contact service center if

poroblem persists

Contact service center

Contact service center

a. Do not use the air

    conditioner if ambient

    temperature is higher than

    52°C(125.6°F)
b. Contact service center if

    problem persists.
c. Replace compressor
a. Turn off and on the unit.
b. Check if drain of

    condensate water is

    working well.

6

WSC-4000 / WSC-6000

Owner’s manual

There is 1 evaporator filter in front of the unit. 

1. loosen up 2 bolts on the front filter guard.

2. Slide filter up and use a vacuum cleaner to remove the dust from the filter.

3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral detergent may be used to

    wash the filter. Do not use any other chemicals to clean filter, as they will likely damage the filter.

4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter

    guard in the closed position.

5. Replace the clean filter and close the filter guard.

NOTE: 

For effective cooling clean the filter at least every 2 weeks.

– Remove dust from the filter

   using a vacuum cleaner

   hose attachment. 

– If required wash the filter in

   lukewarm water with a mild

   detergent. Leave to dry in

   a shaded area before

   reinstalling.

Figure 8 – Removing Filter

Figure 9 – Removal of Dust

Maintenance

FILTER CLEANING

(See Figures 8 and 9)

SELF-DIAGNOSTIC CODES

(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control panel.

The compressor and condenser fan motor will stop operating. The evaporator fan will continue to run for 3 minutes.

If the fault is rectified within 3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes,

the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation.

Customer:

 Please read and keep this manual for future

reference and keep sales receipt as proof of purchase. 

Product

Model No.

Date of Purchase

Place of Purchase

Serial No.

Period of Warranty

Water - cooled split

Portable Air Conditioner

Do not operate without the filter fitted.
Do not operate the unit with a damaged cord or plug, after the unit malfunctions,

or if the unit has been dropped or damaged.

– For your convenience, record the complete model number and product name (located on the Product

   Identification Plate), the purchase date, purchase location, serial number, and warranty period in the table below.

 

– Also, attach your purchase receipt as proof of purchase to this instruction manual for future reference.

 

– To ensure your product is covered by warranty, the complete faulty product along with your original purchase

   receipt must be provided at the place of purchase.

Table 1 – Alarm Codes

Summary of Contents for 6SS12BEA2ACA0

Page 1: ...ot cool or room cool functions The spot cool is designed to deliver very cold air for a continuous amount of time The room cool feature is designed to work with a set point based on room air The unit...

Page 2: ...electrician and all local electrical codes to ensure proper setup Any extension cord used with this device must be rated for a minimum of 15A 18 DO NOT unplug the unit by pulling on the electrical cor...

Page 3: ...haust part discharge of hot air Electrical part Electrical control box Side handle Cooling water air purge control CONDENSER Fresh air inlet for cooling nonfreezing cooling water Caster Figure 2 Figur...

Page 4: ...ther foreign material Do not use the unit in explosive environments or in areas where flammable gas leakage may occur If the power cord or plug is damaged repair should only be performed by qualified...

Page 5: ...be memorized and compressor will stop after the time set Figure 7 5 6SS12BEA2ACA0 6SS24BGA2ACA0 Owner s Manual 5 WSC 4000 WSC 6000 Owner s manual Operation CONTROL PANEL 1 POWER BUTTON Activates unit...

Page 6: ...eration If the fault persists for more than 3 minutes the evaporator fan also stops The fault must be rectified before the unit can resume normal operation Customer Please read and keep this manual fo...

Page 7: ...air filter b Ambient temperature is too high c Cooling pump is not operate normally d Power is not supplied to outdoor unit TH1 outlet temperature sersor has a loose or broken connection TH2 inlet tem...

Page 8: ...8 Owner s Manual 6SS12BEA2ACA0 6SS24BGA2ACA0 Wiring Diagram 8 6SS12BEA2ACA0 6SS24BGA2ACA0 Owner s Manual Wiring Diagram Figure 10 Circuit Wiring Diagram Figure 10 Circuit Wiring Diagram...

Page 9: ...ool 1 Only BlOWER light on ROOM COOL and SPOT COOL light off 2 Compressor will start in 2 minutes after unit is restarting 3 The ambient temperature may be too high 1 Press ROOM COOL button or SPOT CO...

Page 10: ...our dealer for assistance If you cannot reach your dealer or if they cannot resolve the problem call Koldwave Portable Air Conditioner Technical Support at 413 564 5530 Please have the following infor...

Page 11: ...11 Owner s Manual 6SS12BEA2ACA0 6SS24BGA2ACA0...

Page 12: ...2 Owner s Manual 6SS12BEA2ACA0 6SS24BGA2ACA0 260 North Elm St Westfield MA 01085 Phone 413 564 5520 Fax 413 564 5530 www koldwave com For Koldwave warranty please visit http koldwave com warranty aspx...

Reviews: