SELF-DIAGNOSTIC CODES
(See Table 1)
The alarm light is activated if abnormal operation occurs, and a code is displayed on the control
panel. The compressor and condenser fan motor will stop operating. The evaporator fan will
continue to run for 3 minutes. If the fault is rectified within 3 minutes, the unit will resume oper-
ation. If the fault persists for more than 3 minutes, the evaporator fan also stops. The fault must