AIR HANDLING UNIT FUTURE
INSTRUCTIONS FOR OPERATION AND MAINTENANCE
Filter section FSTF
2017-02-13
V. 2.0
15
Filter cassette sizes / number of cassettes
Unit size
Width, mm
Height, mm
287 x 592
592 x 287
592 x 592
592 x 490
2412
2,550
1,350
8
2415
2,550
1,670
4
8
2418
2,550
190
12
2421
2,550
2,310
4
12
2424
2,550
2,550
16
3015
3,190
1,670
5
10
3018
3,190
1,990
15
3021
3,190
2,310
5
15
3024
3,190
2,550
20
3624
3,790
2,550
24
3627
3,790
2,870
6
24
3630
3,790
3,190
30
The thickness of the mounting frame is 25 ±1 mm.
4.7.
Replacement of gasket
Dimensions of the mounting groove and filter cassette frame
A new gasket is mounted, starting from the middle of
the frame bottom. Press the gasket against the edge
of the plate by hand or carefully with a hammer or
some other tool. Use, for example, a 20-mm pipe to
bend the corners appropriately. Cut the gasket to a
length of about 5 mm too long. Force the ends to
-
gether and apply sealant between them.
A. With the clamp closed: 35 ± 1.0
B. Lower frame
C. With the clamp closed: 35 ± 1.0
D. Middle frame