background image

AIR HANDLING UNIT FUTURE

INSTRUCTIONS FOR OPERATION AND MAINTENANCE

Coil sections

2017-02-13 

V. 2.0 

19

5.5. 

Maintenance

• 

Make sure that the water side connections of the coil do not leak.

• 

Make sure that the heat transfer surfaces of the coil are clean and intact.

• 

Clean the coil gently with a brush, compressed air or a vacuum cleaner. If the unit has water drains, the 

coil can be cleaned with water and a mild detergent. 

NOTE! Do not use pressure cleaning.

• 

Bleed the coil and check the operation of the anti-freezing thermostat at the beginning of each heating 

season. 

• 

Check and clean the condensation water discharge system, i.e., drip tray, piping and water trap (traps).

• 

A damaged coil must be repaired in place, sent to the manufacturer to be repaired or replaced.

CAUTION

If the coil is not used during the heating season, water must be drained from it or it has to 

be filled with a water-glycol mixture to avoid freezing. The coil does not drain fully through 

the drain screw; 20 to 30% of the total water volume remains in the coil. To fully drain 

water from the coil, you can, for example, blow compressed air through the bleed screw, 

observing the maximum permissible operating pressure.

CAUTION

The HR circuit must be bled again after 2–4 weeks of heating in order for the energy 

efficiency in heat recovery to be the best possible.

Summary of Contents for 0603

Page 1: ...Instructions for operation and maintenance www koja fi Air handling unit Future...

Page 2: ......

Page 3: ...1 Operating conditions 12 3 2 Commissioning 12 3 3 Maintenance 12 4 Filter section FSTF 13 4 1 Construction 13 4 2 Operating conditions 13 4 3 Installation 13 4 4 Commissioning 13 4 5 Maintenance 14 4...

Page 4: ...section motors and frequency converters 33 12 1 Short circuit motors 34 12 2 Connection of electric motor and frequency converter 36 12 3 PM motors 37 12 4 EC motors 39 12 5 Connection of the EBM Fl...

Page 5: ...on Air handling unit Future complies with the CEN standard EN 1886 classification as follows L2 leakage class for casing T3 heat transfer coefficient for casing 1 3 Sound level For the unit s sound da...

Page 6: ...east 10 mm2 Cu or 16 mm2 Al Alternatively the frequency converter supply can be equipped with an additional protective earth conductor of the same cross section than the actual protective earth conduc...

Page 7: ...must be presented in order to retain the warranty If the motor has to be removed or the fan disassembled due to maintenance or repair work permission is needed from Koja Ltd s Warranty Handler Otherwi...

Page 8: ...ure difference across the filter It indicates the pressure difference and or gives an alarm For the purpose of the filter indicator please refer to the section covering the filters 1 5 3 Fire thermost...

Page 9: ...630 Serial number a conforms with the essential requirements of the directives listed below provided that the said products are installed in accordance with the instructions supplied with the unit Con...

Page 10: ...e access doors In access doors without hinges the earthing conductor must be connected to a quick disconnect connector after attaching the door see picture Earthing of access doors CAUTION The motor o...

Page 11: ...that all shut off and control devices instruments and the signal lamp are functioning The stated maintenance intervals are only guidelines The intervals are determined by the utilisation rate of the a...

Page 12: ...is 40 80 C The maximum permissible pressure difference across the damper is 1 200 Pa 3 2 Commissioning Make sure that the dampers of the sections open and close fully and that the actuator works accor...

Page 13: ...w direction is downwards only The air flow direction is marked on the filter section and on the filters If there are no markings the filter section must be installed so that the air must enter the fil...

Page 14: ...that there are no leaks Check that the filters are clamped in place Check that the differential pressure gauge is intact and reset Check that the differential pressure hoses of the filter section are...

Page 15: ...2 550 24 3627 3 790 2 870 6 24 3630 3 790 3 190 30 The thickness of the mounting frame is 25 1 mm 4 7 Replacement of gasket Dimensions of the mounting groove and filter cassette frame A new gasket is...

Page 16: ...5 1 Operating conditions The maximum operating temperature is 150 C The maximum operating pressure is 1 0 MPa CAUTION The coils of large units have been split in two The condensation water drain of th...

Page 17: ...connection and the left handed according to the figure Left handed connection the heat exchanger must be bled carefully in order to ensure proper fluid circulation in the piping The connection princi...

Page 18: ...control valves to fill the coil with fluid Bleed the coil Make sure that the water side connections of the coil do not leak Check the rotation direction of the circulating pump do not run the pump dry...

Page 19: ...on Check and clean the condensation water discharge system i e drip tray piping and water trap traps A damaged coil must be repaired in place sent to the manufacturer to be repaired or replaced CAUTIO...

Page 20: ...he belt will have allowance for stretch with respect to the limit switch if necessary If necessary adjust the brush seals on the circumference of the rotor so that they touch the surface of the heat e...

Page 21: ...a magnet Twice a year Check and clean the heat transfer surfaces Make sure that the brush seals lightly touch the surface of the heat exchanger Replace damaged brush seals Check the sectorised rotor p...

Page 22: ...cuum cleaner compressed air or water CAUTION If you use a brush make sure not to damage the heat exchanger lamellas CAUTION If you use compressed air point the nozzle perpendicular to the lamellas and...

Page 23: ...Protective casing A B Loosen the rotor mounting bolt Adjust the rotor position with the rotor adjust ment bolts located at the bottom part of the beam Check the rotor position by rotating the rotor by...

Page 24: ...ent of drive belt Tighten the belt around the heat exchanger and pulley Cut the belt to a length that allows it to fit snugly over the pulley When fastened the belt expands automatically to the correc...

Page 25: ...0 25 7 HEAT RECOVERY SECTION PLATE FRTL 7 1 Operating conditions The maximum operating temperature is 80 C The maximum permissible pressure difference between inlet and outlet air is 1 000 Pa 7 2 Inst...

Page 26: ...Dimensioning instructions for water trap The same principles apply to the dimensioning of the water trap in the heat recovery section as to the water trap in the coil section Coil at the inlet side o...

Page 27: ...drains the coil can be cleaned with water and a mild detergent NOTE Do not use pressure cleaning Check and if necessary clean the condensation water discharge system i e drip tray piping and wa ter tr...

Page 28: ...the electrical connections and joints and the direction of air flow which must be according to the arrow marked on the section Give the coil a test run If the overheating protector trips during the te...

Page 29: ...cessary Clean the coil gently with a brush compressed air or a vacuum cleaner If the unit has water drains the coil can be cleaned with water and a mild detergent NOTE Do not use pressure cleaning Che...

Page 30: ...l up with water At the same time make sure that there are no leaks and che ck the operation of the overflow pipe If circulating water is used start the pump when the tray is full of water When the air...

Page 31: ...ntly with a brush compressed air or a vacuum cleaner If the unit has water drains the coil can be cleaned with water and a mild detergent NOTE Do not use pressure cleaning Check and clean the condensa...

Page 32: ...ding to the humidifier manufacturer s instructions 11 2 Commissioning Check the condensation water discharge system i e drip tray piping and water trap Flush the piping and fill the water trap CAUTION...

Page 33: ...the maximum frequency is not exceeded WARNING The motor and or frequency converter supply cables must be equipped with a service switch If the service switch is installed between the motor and frequen...

Page 34: ...manufacturer s instructions The motors are also available with separate therm istors or temperature switches The motors are suitable for frequency converter control Most motors have sealed bearings Mo...

Page 35: ...ctions must be set to approx 10 Hz and maximum frequency instructions according to the fan dependent maximum frequency The current limit is set close to the rated current The frequency converter motor...

Page 36: ...ions Check the electric motor connection from the link box and or the type plate of the motor The electric motor is connected to the electrical network with a shielded connector and equipped with a se...

Page 37: ...he motor in question Parameterisation includes the motor plate values ramps speed and frequency limits as well as settings for starting and stopping The parameters related to the frequency convert er...

Page 38: ...one the connection must be made according to the general EMC requirements The length of the motor cable must not exceed 10 meters The frequency converter supply cable must be equipped with a service...

Page 39: ...er a malfunction This may happen for example if the set point is saved on the fan memory The EC motor control unit parameters and the operation of the control connectors can be changed via the Mod bus...

Page 40: ...rdering the fan so that it can be included in the delivery The current limits are 10 mA for the 10 V output and 40 mA for the 20 V output Do not connect output con nections of various devices with eac...

Page 41: ...limits are 10 mA for the 10 V output and 70 mA for the 24 V output Do not connect output con nections of various devices with each other 12 7 Maintenance spare parts and warranty WARNING The operatio...

Page 42: ...tructions must be followed In case of a discrepancy between these instructions and the component manufacturer s instructions follow the component manufacturer s instructions For the detailed component...

Page 43: ...sure that the inside of the fan section and the fan are free from loose parts debris etc that could get between the belts or the impeller Make sure that the flexible joint and the vibration dampers ar...

Page 44: ...f the fan has grease fittings lubricate the bearings according to the enclosed instructions Replace worn V belt pulleys and V belts If the drive has several grooves all the belts must be replaced at t...

Page 45: ...hoses are in place and intact That the hoses are not flattened out That there are no blockages in the hoses or pressure joints Indicator air flow meter that the air flow meter has been reset and the...

Page 46: ...C fan The fan vibrates produces noise or resonates Check that the impeller is clean and has no external damage Clean the impeller with a vacuum cleaner that has a soft brush nozzle if necessary Contam...

Page 47: ...ll new belts according to the instructions X X Hard particles in the grooves Check the guards replace the belts X X Belts unequally tensioned Follow the installation instructions X X X X X Belts are o...

Page 48: ...and a mild detergent during the annual maintenance or when necessary Those parts of the unit that have water drains can be washed from the inside with running water CAUTION Make sure that the unit ba...

Page 49: ...orption damper The lamellas must be in vertical position see the figure Make sure that the lamellas are intact and that the coating is not damaged 16 2 Maintenance Check that the sound attenuator lame...

Page 50: ......

Page 51: ......

Page 52: ...Tel 358 3 282 5111 koja koja fi www koja com...

Reviews: