3

 

2.10 Risk 

of 

Electrocution 

 

  DANGER 

RISK OF ELECTROCUTION 

DANGER OF DEATH

 

Units supply electrical current while operating; comply with the applicable legislation as well as the 
installation and usage recommendations given in this manual. If you are in any doubt regarding 
installation, please contact your nearest agent. 
Do not connect the unit directly to other power sources (such as the mains for example); fit a source 
changeover panel. 
Never touch stripped cables or disconnected connectors. Never handle a unit with wet hands or feet. 
Never expose the equipment to liquid splashes or rainfall, and do not place it on wet ground. 

 

 

 

2.10.1  Temporary or Semi-temporary Installation (Work site, Show, Fairground, etc.) 

 

A - If the unit is not equipped with an integrated differential protection device at delivery (standard version with insulated neutral on 
the unit's earth terminal): 

-  Use a differential device calibrated to 30mA at the output of each of the unit's sockets (place each device at least 1 meter from 

the unit, protecting it from weather conditions). 

-  If one or more mobile or portable devices are used occasionally, the unit does not need to be earthed. 

B - If the unit is equipped with an integrated differential protection device at delivery (standard version with alternating neutral 

connected to the unit's earth terminal - for use with TT or TN systems): 
-  Connect the unit to the earth: attach a 10 mm

2

 copper wire to the unit's earth terminal (A1) and to a galvanized steel earthing 

rod set 1 meter into the ground. 

 

2.10.2  Fixed Installation or Mains Failure 

 

When supplying a fixed installation (e.g. as backup for mains outages), the unit must be connected by a qualified electrician in 
accordance with the regulations applicable at the installation site. The units are not designed to be connected directly to an 
installation (risk of electrocution or damage to equipment). 
A - If the unit is not equipped with an integrated differential protection device at delivery (standard version with insulated neutral on 

the unit's earth terminal):  

-  Use a source inverter. 
-  The unit does not need to be earthed. 

B - If the unit is equipped with an integrated differential protection device at delivery (standard version with alternating neutral 

connected to the unit's earth terminal - for use with TT or TN systems): 

-  Use a source inverter. 
-  Connect the unit to the earth: attach a 10 mm

2

 copper wire to the unit's earth terminal (A1) and to a galvanized steel earthing 

rod set 1 meter into the ground. 

 

2.10.3 Ground 

Terminal 

 

Ground terminal (A1) connects earth line for prevention of electric shock. When electric device is grounded, be sure to ground 
generator also. 
Connect generator to ground: Attach a 6 AWG (10 mm

2

) copper wire to generator’s ground connection and to a galvanized steel 

grounding rod (not provided) driven 3.3 ft. (1 m) into ground. 

 

2.10.4 Mobile 

Application 

 

The units are intended to operate while stationary. They may not be installed on a vehicle or other mobile equipment unless a study 
has been carried out analysing the unit's various installation and usage specifications. It is prohibited to use the unit whilst it is in 
motion. If earthing is not possible, connect the unit's earth terminal (A1) to the vehicle earth. 

 

2.10.5 Cable 

Selection 

 

For all connections, use flexible, strong rubber-sheathed cables which comply with standard IEC 60245-4 or equivalent cables, and 
ensure that these are kept in perfect condition. Only use one item of class I electrical equipment per socket and connect up 
equipment using a cable equipped with a PE protective conductor (green/yellow); this protective conductor is not required for 
class II equipment. Adhere to the cross sections and lengths recommended in this table during installation or when using electrical 
extensions. 
Equipment type: 

Single-phase 

Three-phase 

Type of unit connector: 

10 A 

16 A 

32 A 

10 A 

16 A 

Recommended cable cross section: 

mm² 

AWG mm² AWG mm² AWG mm² AWG mm² AWG 

Length of 
cable used 

0 to 50 m 

10 

10 

1.5 

14 

2.5 

12 

51 

to 

100 

10 7 10 7 25 3 2.5 12 4 10 

101 

to 

150 

m* 

10 7 16 5 35 2  4 10 6  9 

*This cable length is the maximum permitted length, and must not be exceeded. 
Installation method = cables on raceway or non-drilled tablet/Permitted drop in voltage = 5%/Multi-core conductors/Cable type PVC 70°C (e.g. 
H07RNF)/Ambient temperature =30°C.

 

 

 

Summary of Contents for PRO 3.7

Page 1: ...NT Read all safety precautions and instructions carefully before operating equipment Ensure engine is stopped and level before performing any maintenance or service Record product information to reference when ordering parts or obtaining warranty Specifcation Serial Number Purchase Date ...

Page 2: ...A 9 2 10 5 12 3 8 7 1 17 19 20 22 23 21 13 16 4 24 18 25 11 26 26 15 14 6 ...

Page 3: ...B C H 5 1 2 4 3 1 2 3 4 ...

Page 4: ...nstructions English 2021 Kohler Co All rights reserveed KOHLER CO Kohler Wisconsin 53044 Phone 920 457 4441 Fax 920 459 1646 For the nearest sales service outlet in the US and Canada Phone 1 800 544 2444 KOHLERPower com 2 1 1 3 2 ...

Page 5: ...n switched off and do not operate the unit when animals are in the vicinity fear disturbance etc In all cases respect the local regulations currently in place concerning the use of the units Exhaust gases fuel and oil or coolant if used are toxic products take all necessary protective measures Using a generator indoors CAN KILL YOU IN MINUTES Generator exhaust contains carbon monoxide This is a po...

Page 6: ...after it has been turned off always wait until the engine cools down at least 30 minutes 2 7 Risk of Burns IMPORTANT Before any intervention wait for the unit to cool down at least 30 minutes When running and just after stopping the oil engine and the exhaust silencer are hot and may cause burns if contact is made Never operate the unit with heat shields or guards removed Do not modify the unit Pl...

Page 7: ... source inverter The unit does not need to be earthed B If the unit is equipped with an integrated differential protection device at delivery standard version with alternating neutral connected to the unit s earth terminal for use with TT or TN systems Use a source inverter Connect the unit to the earth attach a 10 mm2 copper wire to the unit s earth terminal A1 and to a galvanized steel earthing ...

Page 8: ...er Neck B2 Fuel Level Indicator A3 CO Sensor Indicator Light A16 Dipstick Upper Limit B3 Fuel Tank Cap A4 Circuit Breaker A17 Dipstick Lower Limit B4 Fuel Valve A5 Change Oil Light A18 Air Filter Cover Screw C1 Air Filter A6 Replace Air Filter Light A19 Air Filter Cover C2 Engine On Off Switch A7 Replace Spark Plug Light A20 Foam Element C3 Choke Lever A8 Low Oil Indicator Light A21 Air Filter Bas...

Page 9: ...he dipstick 3 Insert the oil dipstick filler plug in the filler neck B2 without tightening it then take it out again 4 Visually check the level it must be between the upper limit B3 and lower limit B4 on the dipstick If the oil level is too low open the oil filler cap use a funnel to top up the tank using oil that complies with the specifications in the manual then screw the oil filler plug back i...

Page 10: ...hould be performed on the generator set regularly and carefully by people who have the necessary experience and are equipped with suitable tools in respect of current regulations The maintenance operations to be carried out are detailed in the maintenance table The interval for this is supplied as a guide and for generator sets operating with fuel and oil which conform to the specifications given ...

Page 11: ...n a little clean engine oil and squeeze it to remove any excess oil do not wring it out If there is too much oil remaining in the foam the unit will emit smoke when it is first started 5 Reinstall cover and secure with screw 5 2 4 Replace the Spark Plug When replace spark plug light A20 goes on press reset A22 and follow below maintenance instructions 1 Disconnect the spark plug cap E1 2 Use a dry...

Page 12: ...ar ensuring that the storage procedure is respected afterwards Drain the fuel and change the engine oil 1 Start the unit and allow it to operate until it runs out of fuel l 2 Set the engine on off switch to OFF A7 3 Clean the fuel filter A12 and the sediment bowl A13 C3 4 Close the fuel valve A5 5 Top up the oil Grease the cylinder and valves 6 Remove the spark plug A15 E2 see the section Replace ...

Page 13: ...n only operate while stationary 8 2 Capacity of the Generator Set Before connecting and operating the unit calculate the electrical power required by the units to be used in watts To ensure optimal operation the total wattage of all equipment used at the same time must be greater than 60 of the rated load for the unit risk of insufficient load less than the rated load for the unit during continuou...

Page 14: ...harmful levels of carbon monoxide accumulate around the generator or a CO sensor fault occurs After shutdown the CO sensor indicator light A16 will blink for at least five minutes per the chart below CO sensor DOES NOT replace carbon monoxide alarms Install battery powered carbon monoxide alarm s in your home Don t run generator in enclosed areas Color Description Red Carbon monoxide accumulated a...

Page 15: ...r frame and align screws with bracket holes 3 Thread nuts to screws Torque to 221 in lbs 25 Nm 9 2 Install Leg Kit Tilt unit so fuel tank cap is upward to ensure no fuel leakage A clamping device or an assistant to hold assembly while installing kit will make process easier Leg kit includes 2 legs and mounting hardware Leg kit and wheel kit are designed to be installed together 2 leg kits can be c...

Page 16: ...s Torque to 221 in lb 25 Nm Figure 7 Cord Management Kit 9 6 Install Hand Truck Handle Kit A clamping device or an assistant to hold assembly while installing kit will make process easier Hand truck handle kit includes hand truck handle and mounting hardware 1 Position hand truck handle on unit aligning frame holes and handle holes 2 Place washer between handle and frame 3 While holding in this po...

Page 17: ...ga las legislaciones locales vigentes relativas a la utilización de estos equipos Los gases de escape el carburante y el aceite o el líquido de refrigeración si se utiliza son productos tóxicos adopte todas las medidas de protección necesarias Using a generator indoors CAN KILL YOU IN MINUTES Generator exhaust contains carbon monoxide This is a poison you cannot see or smell NEVER use inside a hom...

Page 18: ...emaduras ATENCIÓN Antes de realizar cualquier intervención espere a que se enfríe el aparato 30 minutos como mínimo Durante el funcionamiento y justo después de la parada el aceite caliente el motor y el silenciador de escape pueden provocar quemaduras en caso de contacto con la piel No utilice nunca el equipo sin las protecciones térmicas o los protectores No modifique el equipo Coloque el equipo...

Page 19: ...s necesario conectar a tierra el equipo B Si el equipo cuenta con dispositivo de protección diferencial integrado en la entrega versión de serie con neutro alterno conectado al terminal de tierra del equipo para uso con sistemas TT o TN Use un inversor de fuente Conecte el equipo a tierra conecte un cable de cobre de 10 mm2 al terminal de tierra del equipo A1 y a una varilla de puesta a tierra de ...

Page 20: ...enado B2 Indicador de nivel de combustible A3 Luz indicadora de sensor de CO alerta de CO A16 Límite superior de varilla de nivel B3 Tapón de depósito de combustible A4 Disyuntor A17 Límite inferior de varilla de nivel B4 Válvula de combustible A5 Luz de cambio de aceite A18 Tornillo de cubierta de filtro de aire C1 Filtro de aire A6 Luz de cambio de filtro de aire A19 Cubierta de filtro de aire C...

Page 21: ... encontrarse entre el límite superior B3 y el inferior B4 de la varilla de nivel Si el nivel de aceite es demasiado bajo abra el tapón de llenado de aceite utilice un embudo para rellenar el depósito con aceite que cumpla las especificaciones del manual y vuelva a enroscar el tapón de llenado de aceite Si el nivel de aceite es demasiado alto proceda a un vaciado parcial con ayuda de un recipiente ...

Page 22: ...e el equipo esté bien ventilado y para evitar cualquier riesgo de incendio espere a que se enfríe completamente antes de cubrirlo y guardarlo Incluso cuando el equipo está apagado el motor sigue emitiendo calor Capítulo 5 Mantenimiento del grupo electrógeno Como medida de seguridad el mantenimiento del grupo electrógeno debe llevarse a cabo con regularidad y con precaución del mismo deben encargar...

Page 23: ...2 y siga las instrucciones de mantenimiento 1 Retire el tornillo C1 y la cubierta del filtro de aire C2 2 Retire el elemento de espuma C3 de la base del filtro de aire C4 3 Limpie el elemento de espuma lávelo con agua y jabón enjuáguelo cuidadosamente y deje que se seque totalmente 4 Sumerja el elemento de espuma en una pequeña cantidad de aceite de motor limpio y presiónelo para eliminar el exces...

Page 24: ...íe el combustible y cambie el aceite de motor 1 Arranque el aparato y déjelo funcionar hasta que se detenga por falta de combustible 2 Coloque el interruptor de encendido apagado del motor en la posición de apagado A7 3 Limpie el filtro de combustible A12 y la cubeta de sedimentos A13 C3 4 Cierre la válvula de combustible A5 5 Renueve el aceite Lubrique el cilindro y las válvulas 6 Retire la bujía...

Page 25: ... C adicionales o aproximadamente un 1 por cada 100 m adicionales de altitud Los equipos solo pueden usarse estando inmóviles 8 2 Capacidad del grupo electrógeno Antes de conectar y usar el equipo calcule la potencia eléctrica que necesitan los equipos que van a usarse en vatios Para garantizar un funcionamiento óptimo la potencia total de todos los equipos utilizados al mismo tiempo debe ser super...

Page 26: ...rógeno o se produce una avería en la sensor de CO alerta de CO Después de apagar el equipo la luz del indicador de sensor de CO alerta de CO A16 parpadeará durante al menos cinco minutos según indica el cuadro de más abajo La sensor de CO alerta de CO NO sustituye a las alarmas de monóxido de carbono Instale en su hogar una o varias alarmas de monóxido de carbono con batería No use el grupo electr...

Page 27: ...ue las tuercas en los tornillos Par de apriete 25 Nm 221 in lb 9 2 Instalación de kit de patas Incline el equipo para que la tapa del depósito de combustible quede hacia arriba para garantizar que no haya fugas de combustible El proceso será más fácil con un dispositivo de sujeción o una persona que sostenga el conjunto mientras se instala el kit El kit de patas incluye 2 patas y la tornillería de...

Page 28: ...it de organización de cables 9 6 Instalación del kit de empuñadura tipo carro de carga El proceso será más fácil con un dispositivo de sujeción o una persona que sostenga el conjunto mientras se instala el kit El kit de empuñadura de tipo carro de carga incluye la empuñadura de carro de carga y la tornillería de montaje 1 Coloque la empuñadura de carro de carga en el equipo alineando los orificios...

Reviews: