20 Reconnection/Adjustments
TP-6034 10/02
100--120/200--240-Volt Configurations
The 100--120/200--240-volt configuration does not use
a jumper lead. If the unit was originally wired for straight
100--120 volt, 3 wire, remove the jumper lead (see
Figure 8-1 for location).
Select a two-pole circuit
breaker. Application of two single-pole circuit breakers
does not conform to NEC requirements for supplying a
200--240 volt
load—even
if
the
breakers
are
mechanically attached.
Leads L1 and L2 are for
different phases—
never
connect them.
4
3
2
1
Stator Leads
L0
GRD.
L2
L1
L0 (Neutral)
Line
Side
Factory
Two-Pole
Circuit
Breaker
Ground
Load
Side
100--120/200--240 Volt,
3 Wire
60 Hz
50 Hz
L0--L1
100--120 Volt
100--120 Volt
L0--L2
100--120 Volt
100--120 Volt
L1--L2
200--240 Volt
200--240 Volt
Figure 8-3
100--120/200--240-Volt,
3-Wire Configuration
200--240-Volt Configurations
The 200--240-volt configuration does not use a jumper
lead.
If the unit was originally wired for straight
100--120 volt, 3 wire, remove the jumper lead (see
Figure 8-1 for location).
4
3
2
1
Stator Leads
L0
GRD.
L1
L0 (Neutral)
Line
Side
Single-Pole
Circuit
Breaker
Ground
Load
Side
200--220--240 Volt,
2 Wire
Tape to insulate
from ground
60 Hz
L0--L1
not used
200--220--240 Volt
50 Hz
Figure 8-4
200--220--240-Volt,
2-Wire Configuration
Summary of Contents for 7ER
Page 1: ...Commercial Mobile Generator Sets Model 7ER TP 6034 10 02a Installation...
Page 2: ......
Page 4: ...TP 6034 10 02 Table of Contents Notes...
Page 10: ...VI Safety Precautions and Instructions TP 6034 10 02 Notes...
Page 12: ...2 Introduction TP 6034 10 02 Notes...
Page 16: ...6 Cooling System TP 6034 10 02 Notes...
Page 28: ...TP 6034 10 02 18 Installation Drawing Notes...
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......