TP-6034 10/02
Cooling System 5
Section 3 Cooling System
3.1 Air Requirements
Air flow around the generator set is necessary for
adequate cooling.
See the current generator set
specification sheet for air requirements. The air intake
silencer/cleaner provides combustion air to the engine.
See Figure 3-1 for allowable intake restriction.
The
engine/generator
performance
will
be
adversely
affected if these guidelines are neglected. Follow these
guidelines to optimize generator set performance.
Model
Normal Intake Restriction
7ER
0.03 psi (0.79 in. H
2
O)
Figure 3-1
Intake Restriction
3.2 High Water Temperature
Switch
Each generator set includes a high water temperature
shutdown switch that automatically shuts down the set if
operating temperatures climb too high.
Follow the
guidelines
described
in
Section
3.1
to prevent
shutdowns.