Kohler 4EFRKM Operation Download Page 29

TP-6081 4/00

17

Section 4 Troubleshooting

Trouble Symptoms

Probable Causes

Generator

set does not

crank

Generator

set cranks

but does

not start

Generator

set starts

hard

No or low
generator

voltage

Generator

set stops
suddenly

Generator

set lacks

power

Generator

set

overheats

Low/High

oil

pressure

High fuel

consumption

Excessive

or

abnormal

noise

Section/

Publication

Reference

Actions

Air cleaner clogged

x

x

x

x

3.5

Clean or replace.

Engine overload

x

x

x

x

I/M

Reduce electrical load. See the installation manual for wattage requirements.

Compression weak

x

x

x

x

x

x

Engine S/M

Check the compression.*

Exhaust system leak

x

x

3.6

Inspect the exhaust system. Replace the inoperative exhaust system components.*

e

Exhaust system not securely installed

x

3.6

Inspect the exhaust system. Tighten the loose exhaust system components.*

gine

Governor inoperative

x

x

x

x

S/M

Adjust the governor.*

En

g

Valve clearance incorrect

x

x

x

Engine S/M

Adjust the valves.*

Excessive vibration

x

Tighten all loose hardware.

Inadequate cooling

x

x

x

3.7

Check air intake/cooling areas.

Inoperative or improper gap of spark plug

x

x

x

3.8

Regap or replace spark plug

be

Incorrect crankcase oil type for ambient temperature

x

x

x

x

3.3.4

Change the oil. Use oil with a viscosity suitable for the operating climate.

Lub

e

Oil level low

x

x

x

3.3.2

Restore the oil level. Inspect the generator set for oil leaks.

Battery connections loose, corroded, or incorrect

x

x

3.9

Verify that the battery connections are correct, clean and tight.

Battery weak or dead

x

x

3.9

Recharge or replace the battery.

Starter/starter solenoid inoperative

x

x

S/M

Replace the starter or starter solenoid. *

cal

Engine harness twist-lock connector not locked tight

x

x

x

Disconnect the engine harness twist-lock connector then reconnect it to the controller.

ct

ric

a

Loose or inoperative spark plug wire

x

x

x

x

x

3.8

Reconnect or replace wire

Ele

c

Fault shutdown

x

S/M

Reset the fault switch(es) and troubleshoot the controller. *

Inoperative ignition module

x

x

x

x

Engine S/M

Test and/or replace. *

Voltage regulator inoperative or out of adjustment

x

x

x

S/M

Replace the voltage regulator fuse. Excite the main field separately.*

Inoperative controller circuit board

x

x

x

S/M

Replace the controller circuit board. *

ol

Tripped controller circuit breaker, if equipped

x

x

2.4.1

Reset the controller circuit breaker.

ontrol

Controller fault

x

S/M

Troubleshoot the controller.*

Co

n

Blown controller fuse

x

x

x

S/M

Replace the blown controller fuse. If the fuse blows again, troubleshoot the controller.*

Inoperative controller start/stop switch

x

x

S/M

Replace the start/stop switch. *

Inoperative choke heater

x

x

x

x

Engine S/M

Check operation. *

Fuel tank empty or fuel valve shut off

x

x

3.4.1

Add fuel and move the fuel valve to the ON position.

Inoperative electric fuel pump

x

x

x

x

S/M

Test the fuel pump. *

F

uel

Fuel old or dirty

x

x

x

3.4.1

Replace fuel

F

Fuel vapor lock

x

Check the fuel line routing.

Inoperative antidieseling solenoid

x

x

x

S/M

Check operation.*

Open AC output circuit breaker

x

2.4.1

Reset the breaker and check for AC voltage at the generator side of the circuit breaker.

r

Transfer switch main power contacts in the OFF position

x

Turn the switch to the auto position.

rator

Open wiring, terminals, or pin in the exciter field

x

S/M

Check for continuity. *

ener

a

Inoperative main field (rotor) (open or grounded)

x

S/M

Test and/or replace the rotor.*

G

e

Inoperative stator (open or grounded)

x

S/M

Test and/or replace the stator.*

Excessive vibration

x

S/M

Tighten loose components.*

*

Have an authorized service distributor/dealer perform this service.

Summary of Contents for 4EFRKM

Page 1: ...Commercial Mobile Generator Sets Models 5ERKM 4EFRKM TP 6081 4 00 Operation...

Page 2: ...Engine exhaust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING California Proposition 65...

Page 3: ...et 4 2 4 3 Stopping the Generator Set 4 Section 3 Scheduled Maintenance 5 3 1 General Maintenance 5 3 2 Service Schedule 6 3 3 Lubrication System 8 3 3 1 Oil Specifications 8 3 3 2 Oil Check 8 3 3 3 O...

Page 4: ...TP 6081 4 00 Table of Contents Notes...

Page 5: ...t the power to the battery charger if equipped 2 Remove the battery cables negative lead first Reconnect the negative lead last when reconnecting the battery Follow these precautions to prevent the st...

Page 6: ...to the following D Light headedness dizziness D Physical fatigue weakness in joints and muscles D Sleepiness mental fatigue inability to concentrate or speak clearly blurred vision D Stomachache vomi...

Page 7: ...whenever electricity is present Open the main circuit breakers of all power sources before servicing the equipment Configurethe installation to electrically ground the generator set transfer switch a...

Page 8: ...thecrankshaft hardwareorrotorthrubolt whenmaking adjustments or servicing the generator set Rotate the crankshaft manually in a clockwise direction only Turning the crankshaft bolt or rotor thrubolt c...

Page 9: ...Assistance Service Information Please contact a local authorized distributor dealer for sales service or other information about Kohler Generator Division products To locate a local authorized distri...

Page 10: ...readily available for future reference Record field installed kit numbers after installing the kits Generator Set Identification Numbers Record the product identification numbers from the generator s...

Page 11: ...23316 Spark Plug 63 132 01 S Spray Paint Black 221292 Voltage Regulator Fuse 10 amp 223316 Figure 1 Maintenance and Service Parts x in 001 004 List of Related Literature Figure 2 identifies related li...

Page 12: ...TP 6081 4 00 iv Maintenance and Service Parts Related Literature Notes...

Page 13: ...ide 11 Lifting eye 12 Muffler 13 Exhaust outlet nonservice side 14 Spark plug 15 Air cleaner 16 Carburetor 17 Oil drain valve 18 Oil check oil fill 19 Fuel feed pump 20 Fuel inlet 21 Cooling air inlet...

Page 14: ...TP 6081 4 00 2 Section 1 Service Views Notes...

Page 15: ...vel Check the fuel level and keep the tank s full to ensure adequate fuel supply Oil Level Maintain the oil level at or near not over the full mark on the dipstick Operating Area Check for obstruction...

Page 16: ...arging Fuse This fuse protects the battery charging circuitry Voltage Regulator Fuse This fuse protects the voltage regulator circuitry Remote Start Connector A 6 pin connector on the controller s bac...

Page 17: ...use bothAmericanStandardandmetrichardware Usethecorrect size tools to prevent rounding of the bolt heads and nuts See the Safety Precautions and Instructions at the beginning of this manual before att...

Page 18: ...nkcase 3 3 4 X 20 hrs break in period X COOLING SYSTEM Check the air intake and cooling areas for obstructions and clean as necessary X Check X Clean IGNITION SYSTEM Check the spark plug condition adj...

Page 19: ...nd have it serviced if necessary X ENGINE AND MOUNTING Check for fuel and oil leakage X Retighten all nuts and bolts X Check the mounting bolts vibromounts and tighten as necessary X 200 hrs Check and...

Page 20: ...ove it Maintain the oil level between the Full and Add marks on the dipstick as shown in Figure 3 2 See Section 1 Service Views for the dipstick location 1 TP 5586 3 2 1 Full mark 2 Add mark Figure 3...

Page 21: ...t Dispose of used engine oil and other contaminants in a safe approved manner 3 4 Fuel System 3 4 1 Fuel Specifications Use a clean good quality unleaded fuel with an octane number of 87 Use fresh gas...

Page 22: ...s occupants install a carbon monoxide detector Consult the coach builder or dealer for approved detector location and installation Inspect the detector before each generator set use In addition to rou...

Page 23: ...Gap bridged spark plug Built up deposits and gap between the electrodes closing Oil or carbon fouling Clean and regap the spark plug Oil fouled spark plug Wet black deposits on the insulator shell bor...

Page 24: ...mm 0 028 0 031 in 7 Use a gapping tool to gently bend the side electrode closer to or farther from the center electrode to set the correct gap See Figure 3 6 Position the side electrode directly over...

Page 25: ...cid Battery gases Explosion can cause severe injury or death Battery gases can cause an explosion Do not smoke or permit flames or sparks to occur near a battery at any time particularly when it is ch...

Page 26: ...d moisture from mixing with the fuel 5 Remove the spark plug Pour approximately 1 tablespoon of engine oil into the spark plug hole Crank the engine two or three revolutions to lubricate the cylinder...

Page 27: ...he generator set installation manual I M and the engine service manual Engine S M to correct the indicated problem Corrective action and testing often require knowledge of electrical and electronic ci...

Page 28: ...TP 6081 4 00 16 Section 4 Troubleshooting Notes...

Page 29: ...ot locked tight x x x Disconnect the engine harness twist lock connector then reconnect it to the controller ctrica Loose or inoperative spark plug wire x x x x x 3 8 Reconnect or replace wire Elec Fa...

Page 30: ...TP 6081 4 00 18 Section 4 Troubleshooting Notes...

Page 31: ...gative lead last when reconnecting the battery Follow these precautions to prevent the starting of the generator set by the remote start stop switch Hazardous voltage Can cause severe injury or death...

Page 32: ...TP 6081 4 00 20 Section 5 Diagrams and Drawings GM11960 Figure 5 1 Schematic Wiring Diagram...

Page 33: ...TP 6081 4 00 21 Section 5 Diagrams and Drawings GM11960 Figure 5 2 Point to Point Wiring Diagram...

Page 34: ...TP 6081 4 00 22 Section 5 Diagrams and Drawings Notes...

Page 35: ...e CWC city water cooled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dBA decibel A weighted DC direct current DCR direct current resistance deg degree dept department...

Page 36: ...onal Safety and Health Administration O V overvoltage oz ounce p pp page pages PA packed accessory PC personal computer PCB printed circuit board pF picofarad PF power factor ph phase PHC Phillips hea...

Page 37: ...Log Use the log below to keep a cumulative record of operating hours on your generator set and the dates required services were performed Enter hours to the nearest quarter hour OPERATING HOURS SERVIC...

Page 38: ...TP 6081 4 00 A 4 Appendix Notes...

Page 39: ......

Page 40: ...381 Web site www kohlergenerators com Fax 920 459 1646 U S A Sales Fax 920 459 1614 International For the nearest sales and service outlet in U S A and Canada Phone 1 800 544 2444 Kohlerr Power System...

Reviews: