TP-6862 6/14
20 Section 4 Exhaust System
4.4.2
Mid/Below-Waterline Installation
Follow USCG regulations for installing an antisiphon
provision to prevent raw water entry into the engine.
Use the siphon break if the exhaust manifold outlet is
located less than 23 cm (9 in.) above the waterline when
the craft is loaded to maximum capacity. Install the
siphon break at least 31 cm (1 ft.) above the waterline
using the instructions provided with the siphon break kit.
Note:
An improperly installed siphon break will cause
engine damage and may void the warranty.
Install the siphon break above the highest point in the
exhaust line between the heat exchanger and the
exhaust mixer. See Figure 4-6 for the siphon break
connection. Support the siphon break and hoses to
maintain their position and function. Allow a slight offset
to clear the stringers or other permanent structures.
Protect the siphon break air inlet from dirt and debris.
Note:
To prevent water leakage on the generator set, do
not mount the siphon break directly over the
generator set.
Note:
Ensure that the siphon break’s cap is tight before
operating the generator set.
1
ADV8501B-
1. Cut hose and connect siphon break and hardware
Non-Service Side View
Figure 4-6
Siphon Break Connection (Typical for
Non-Sound Shielded Units)
Mount a typical silencer’s base no more than 1.2 m (4 ft.)
below the highest point in the exhaust line. Attach a
separate wood mounting base to the hull stringers or
other suitable structures.
Use the silencer
manufacturer’s recommendation for securing the
silencer to the hull. Mount the silencer with the outlet not
more than 3 m (10 horizontal ft.) from the engine’s
exhaust manifold outlet. Use a USCG-type certified
marine exhaust hose.
Summary of Contents for 33-125EFOZCJ
Page 2: ...TP 6862 6 14 2...
Page 8: ...TP 6862 6 14 8 Safety Precautions and Instructions Notes...
Page 10: ...TP 6862 6 14 10 Section 1 Introduction Notes...
Page 12: ...TP 6862 6 14 12 Section 2 Location and Mounting Notes...
Page 28: ...TP 6862 6 14 28 Section 5 Fuel System Notes...
Page 34: ...TP 6862 6 14 34 Section 6 Electrical System Notes...
Page 52: ...TP 6862 6 14 52 Section 7 Installation Drawings Notes...
Page 78: ...TP 6862 6 14 78 Section 9 Paralleling Generator Sets Notes...
Page 82: ...TP 6862 6 14 82...
Page 83: ...TP 6862 6 14 83...