TP-6862 6/14
29
Section 6 Electrical System
Section 6 Electrical System
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Moving parts.
WARNING
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death.
Connect the
generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is turned off. Backfeed connections can cause
severe injury or death to utility personnel working on power
lines and/or personnel near the work area. Some states and
localities prohibit unauthorized connection to the utility
electrical system. Install a ship-to-shore transfer switch to
prevent interconnection of the generator set power and shore
power.
6.1 AC Voltage Connections
Make AC connections to the generator set inside the
junction box. Typically, the generator set connects to a
ship-to-shore transfer switch that allows the use of
shore/utility power when docked or generator set power
when docked or at sea. The wiring then connects to a
main circuit breaker box (panel board) that distributes
branch circuits throughout the craft. See Section 8 for
reconnection of the generator set.
6.2 Circuit Protection
The AC circuit breakers (optional) protect the wiring
from the AC circuit breakers to the vessel’s distribution
panel. AC circuit breakers trip when they detect a fault in
the output circuit.
After correcting the fault, reset the AC circuit breaker(s) by
placing them in the ON position. Restart the unit. Do not
start the unit under load. See Figure 6-1 and Figure 6-2
for AC circuit breaker ratings.
The unit’s voltage
configuration determines the circuit breaker selection.
Note:
Circuit breaker ampere rating and availability are
subject to change.
6.2.1
Circuit Breaker Considerations
Mounting location.
Mount the circuit breakers in the
generator set’s junction box. See Section 6.2.2.
Sizing
.
Use the generator set voltage/frequency
configuration to determine the circuit breaker
amperage. If the generator set voltage configuration
changes, change the circuit breaker to provide optimum
protection.
For circuit breaker application
and selection
information, contact an authorized distributor/dealer.
Have a qualified electrician or technician install circuit
breakers and reconnect the generator set. Comply with
all governing standards and codes.
Amps
Max.
Voltage
Model(s)
70
600
40EOZD(C)DJ, 33EFOZD(C)J
80
600
40EFOZD(C)J, 45EFOZD(C)J
90
480
40EFOZD(C)J, 45EFOZD(C)J
100
480
55EOZD(C)J, 45EFOZD(C)J, 50EFOZD(C)J
125
480
50EFOZD(C)J, 65EOZD(C)J, 55EFOZD(C)J
125
600
33EFOZD(C)J
150
480
80EOZD(C)J, 70EFOZD(C)J
150
600
40EOZD(C)J, 33EFOZD(C)J, 40EFOZD(C)J
175
480
99EOZD(C)J, 70EFOZD(C)J 80EFOZD(C)J
175
600
40EOZD(C)J, 33EFOZD(C)J, 40EFOZD(C)J,
45EFOZD(C)J
200
600
40EFOZD(C)J, 50EFOZD(C)J, 55EOZD(C)J
250
600
50EFOZD(C)J, 55EOZD(C)J, 45EFOZD(C)J,
65EOZD(C)J, 55EFOZD(C)J, 125EOZD(C)J,
100EFOZDJ(C)J
400
600
80EOZD(C)J, 70EFOZD(C)J, 99EOZD(C)J,
80EFOZD(C)J, 150EOZD(C)J,
100EFOZD(C)J, 125EFOZD(C)J
600
600
125EOZD(C)J 150EOZD(C)J,
100EFOZD(C)J, 125EFOZD(C)J
Figure 6-1
3-Pole AC Circuit Breaker Ratings
(33--150 kW Models), Listed By Amps
Summary of Contents for 33-125EFOZCJ
Page 2: ...TP 6862 6 14 2...
Page 8: ...TP 6862 6 14 8 Safety Precautions and Instructions Notes...
Page 10: ...TP 6862 6 14 10 Section 1 Introduction Notes...
Page 12: ...TP 6862 6 14 12 Section 2 Location and Mounting Notes...
Page 28: ...TP 6862 6 14 28 Section 5 Fuel System Notes...
Page 34: ...TP 6862 6 14 34 Section 6 Electrical System Notes...
Page 52: ...TP 6862 6 14 52 Section 7 Installation Drawings Notes...
Page 78: ...TP 6862 6 14 78 Section 9 Paralleling Generator Sets Notes...
Page 82: ...TP 6862 6 14 82...
Page 83: ...TP 6862 6 14 83...