TP-6137 5/03
34
Section 6 Cooling System
Waterline
4
5
13
6
7
8
9
10
11
12
15
14
3
2
1
TP-5586-3
1. Silencer vertical lift 1.2 m (4 ft.) max.
2. Exhaust outlet distance from the waterline. Use a siphon break if
the exhaust mixer outlet is located less than 23 cm (9 in.) above
the waterline.
3. Siphon break distance above waterline 30.5 cm (1 ft.) min.
4. Siphon break
5. Exhaust outlet
6. Seawater strainer
7. Seacock
8. Intake strainer
9. Gear-driven seawater pump
10. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
11. Water lock (optional)
12. Silencer distance from exhaust outlet 3 m (10 ft.) max.
13. Silencer (customer supplied)
14. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
15. Exhaust outlet distance above the waterline 10 cm (4 in.) min.
Figure 6-6
Siphon Break, Plastic “U” Type
Note:
Do not locate the siphon break directly above the
generator set.
Summary of Contents for 3.5EFOZ
Page 1: ...Marine Generator Sets Includes Engine Maintenance Models 4EOZ 3 5EFOZ TP 6137 5 03 Service ...
Page 10: ...TP 6137 5 03 VI Safety Precautions and Instructions Notes ...
Page 12: ...TP 6137 5 03 ii Service Assistance Notes ...
Page 28: ...TP 6137 5 03 16 Section 3 Scheduled Maintenance Notes ...
Page 42: ...TP 6137 5 03 30 Section 5 Fuel System Notes ...
Page 48: ...TP 6137 5 03 36 Section 6 Cooling System Notes ...
Page 102: ...TP 6137 5 03 90 Section 10 Generator and Engine Disassembly Reassembly Notes ...
Page 104: ...TP 6137 5 03 92 Section 11 Wiring Diagrams 11 1 Wiring Diagram Schematic GM20645 B ...
Page 105: ...TP 6137 5 03 93 Section 11 Wiring Diagrams 11 2 Wiring Diagram Point to Point GM20645 B ...
Page 106: ...TP 6137 5 03 94 Section 11 Wiring Diagrams Notes ...
Page 114: ......
Page 115: ......