TP-6517 1/11
37
Section 4 Scheduled Maintenance, 18 kW Models
Clean the battery and cables and tighten battery
terminals using the service schedule recommendations.
To prevent corrosion, maintain tight, dry electrical
connections at the battery terminals.
To remove
corrosion from battery terminals, disconnect the cables
from the battery and scrub the terminals with a wire
brush. Clean the battery and cables with a solution of
baking soda and water. After cleaning, flush the battery
and cables with clean water and wipe them with a dry,
lint-free cloth.
After reconnecting the battery cables, coat the battery
terminals with petroleum jelly, silicone grease, or other
nonconductive grease.
4.9 Battery Charger
The
generator
set
is
equipped
with
a
6-amp
float/equalize battery charger to maintain the engine
starting battery.
Figure 4-8 illustrates the battery
charger.
The charger’s DC leads are factory-wired. Periodically
tighten all connections.
INDICATOR
Red:
Red & Green:
Green:
VOLTS= 11.8--14.0
AMPS= 5.0--6.0
VOLTS= 14.0--14.5
AMPS= 1.5--5.0
VOLTS= 13.0--13.6
AMPS= 0.1--1.5
CAUTION:
To reduce the risk of elect rical shock,
connect only to properly gr ounded outlet.
Allowable Battery Types: Lead Acid a
nd Gel Cell
INPUT: 115 VAC 50/60Hz @ 1.6A
OUTPUT: 12 VDC @ 6 Amps
MAX. BAT.: 180 Amp Hr. Max.
DATE:
6 AMP AUTOMATIC
BATTERY CHARGER
R
C
US LISTED
BATTERY CHARGER
53AB
2608KH
1
1. LED indicators
2. Mounting flanges
3. AC power cord
2
5
2
3
4
4. Fuse
5. Battery leads, 12 VDC
Figure 4-8
6-Amp Float/Equalize Battery Charger
4.10 Circuit Protection
If the generator set circuit breaker trips or the fuses blow
repeatedly, see Section 5, Troubleshooting, for possible
causes.
4.10.1 Line Circuit Breaker
A line circuit breaker interrupts the generator output in
the event of a fault in the wiring between the generator
and the load. The line circuit breaker location is shown
in Figure 1-2. The circuit breaker rating is shown in
Figure 4-9. If the circuit breaker trips, reduce the load
and switch the breaker back to the ON position. With the
breaker in the OFF position the generator set runs but
the generator output is disconnected from the load.
Model
Circuit Breaker Rating, Amps
18 kW
80
Figure 4-9
Line Circuit Breaker Rating
4.10.2 Fuses
Three panel-mounted fuses protect the alternator and
electrical controls. See Section 1.5 for fuse locations.
Another 10-amp fuse protects the battery charger. See
Figure 4-8 for the battery charger fuse location.
See Figure 4-10 for fuse part numbers. Always identify
and correct the cause of a blown fuse before restarting
the generator set. Refer to Section 5, Troubleshooting,
for conditions that may indicate a blown fuse. Replace
blown fuses with identical replacement parts.
Fuse
Rating, Amp
Label
Part Number
Auxiliary winding
20
F1
292937
Relay interface
board
10
F2
223316
Controller
10
F3
223316
Battery charger
10
—
AGS 10
Figure 4-10
Fuses
Summary of Contents for 12RESL
Page 14: ...TP 6517 1 11 14 Section 1 Features Notes...
Page 20: ...TP 6517 1 11 20 Section 2 Operation Notes...
Page 30: ...TP 6517 1 11 30 Section 3 Scheduled Maintenance 12 kW Models Notes...
Page 42: ...TP 6517 1 11 42 Section 5 Troubleshooting Notes...
Page 45: ...Notes...
Page 46: ...Notes...
Page 47: ......