TP-6517 1/11
32
Section 4 Scheduled Maintenance, 18 kW Models
4.2 Service Schedule, 18 kW Models
System Component or Procedure
See
Section
Procedure
Visually
Inspect
Check
Change
Clean
Test
Fuel
Flexible lines and connections
Q
R
Main tank supply level
W
Fuel piping
Y
Lubrication
4.3
Oil level
8 or E
Change oil
Y or 150
Replace filter
Y or 150
Crankcase breather hose
Y or 500
Oil cooler
Y
Y or 100
Cooling
4.6
Air ducts, louvers
Y
Y
Exhaust System
4.7
Leakage
W
W
Insulation, fire hazards
Y
Obstructions or combustible materials near exhaust outlet
W
DC Electrical System
4.8
Battery charger operation, charge rate
M
Remove corrosion, clean and dry battery and rack
Y
Y
Clean and tighten battery terminals and inspect boots
Y
Y
Battery electrolyte level and specific gravity *
Y
AC Electrical System
Tighten control and power wiring connections
Y
Remote control system, if equipped
M
Visible wear or damage
Q
Wire abrasions where subject to motion
6 months
6 months
Wire-cable insulation condition
3Y or 500
Engine and Mounting
Visible wear or damage
W
Air cleaner service
[
4.5
150
300
Spark plugs
4.4
150
300
Replace stepper motor coupling and bushing
S/M
500 (D)
Generator
Visible wear or damage
2.1
Q
Exercise generator set
2.5
W
Brushes and collector ring
S/M
Y (D)
Y (D)
Measure and record resistance readings of windings with
insulation tester (Megger
r
, with SCR assembly or rectifier and
load leads disconnected)
S/M
3Y (D)
General Condition of Equipment
Evidence of vibration, leakage, deterioration, unusual or
excessive noise or temperature
W
W
W
Interior of sound enclosure
Q
Q
* Not necessary for maintenance-free batteries.
[
Service more frequently under extremely dusty/dirty conditions.
Megger
r
is a registered trademark of Biddle Instruments.
E
Each use
W
Weekly
M
Monthly
Q
Quarterly
Y
Yearly
Number = hours of operation
D
Authorized distributor/dealer only
R
Replace as necessary
S/M Service Manual
Summary of Contents for 12RESL
Page 14: ...TP 6517 1 11 14 Section 1 Features Notes...
Page 20: ...TP 6517 1 11 20 Section 2 Operation Notes...
Page 30: ...TP 6517 1 11 30 Section 3 Scheduled Maintenance 12 kW Models Notes...
Page 42: ...TP 6517 1 11 42 Section 5 Troubleshooting Notes...
Page 45: ...Notes...
Page 46: ...Notes...
Page 47: ......